INSTALLATION CHECKLIST
MODELS 125B / 125BL / 125BS / 125X
GAS LINE SIZE
Natural Gas
Nominal Iron Pipe Size* 1/2" 3/4" 1"
MAXIMUM LENGTH
10' 40' 150'
Liquid Propane
Semi-rigid Tubing 1/2" 5/8" 3/4" 7/8"
MAXIMUM LENGTH
NOT
RECOMMENDED
20' 60' 150'
* Flex tubing greatly reduces capacity and, therefore, is not recommended.
Minimum Vent Size* and Height
Minimum Diameter Minimum Height**
5 inches 6 feet
* NOTE
: Vent size must not be restricted. Installation must comply with national fuel
g
as code ventin
g
requirements
for a 117,000 Btu Cate
g
ory I appliance and any applicable local codes.
Water Pressure
For installation on well systems, insure that your water pressure is between 30 - 50 psi.
** NOTE
: Minimum vent hei
g
ht must be 6 feet, provided there are no elbows. Termination of the vent must be 2
feet above any obstructionwithin a 10 foot radius of vent pipe. Consult your
g
as utility or National Gas Fuel Code if
vent will have elbows or share ventin
g
with another appliance. The vent connector should have as much vertical
rise as possible (minimum 12") before any horizontal run.