Installation Instructions

4
Supply power wire A:
Multipolar electric wire. Size and length of the suggested electric wire are showed on table “electrical data”. The wire
must be Mod. H07RN-F (according to CEI 20-19 CENELEC HD 22). Make sure the length of the conductors between
the fixing point and the terminals allows the straining of the conductors L, N before that of the grounding.
Connecting wire B (SHIELDED):
Bipolar electric shielded wire; size and length of the suggested electric wire are showed on table “electrical data”.
The wires have not to be lighter than Mod. H05VVC4V5-K (according to CEI 20-20 CENELEC HD21).
Connecting wire C (with ground conductor):
Multipolar electric wire; size and length of the suggested electric wire are showed on table “electrical data”. The
wires have not to be lighter than Mod. H07RN-F (according to CEI 20-19 CENELEC HD22).
MODEL
mm
2
DUAL SPLIT
MONO SPLIT
L ("C") m
1,5
15
0,75
≤ 25
1,5
≤ 25
L ("A") m
L ("B") m
15
≤ 20
≤ 20
10 A
LENGTH, SIZE WIRES AND DELAYED FUSE
ADDITIONAL MATERIAL REQUIRED FOR INSTALLATION (NOT SUPPLIED)
NARROW TUBE LARGE TUBE
MODEL (INDOOR UNIT)
OUTER DIAMETER MIN. THICKNESS OUTER DIAMETER MIN. THICKNESS
A 6,35 mm 0,8 mm 9,52 mm 0,8 mm
B - C 6,35 mm 0,8 mm 12,7 mm 0,8 mm
Deoxidized annealed copper tube for refrigerant tubing connecting the units of the system; it has to be insulated with foamed polyethylene
(min. thickness 8mm).
PVC pipe for condensate drain pipe (ø int.18mm) in length suitable to let the condensate flow into the outside drainage.
Anti-freeze oil for flare connections (about 30g.).
Electric wire: use insulated copper wires of size and length as shown at paragraph “SYSTEM WIRING DIAGRAMS”.
TUBING LENGTH AND ELEVATION DIFFERENCE LIMITS
L Tot. (m) L n (m) L Tot. (m) L n (m)
AEI1G42EMX
MONO SPLIT
12 - 20 -
AEI1G50EMX/BB DUAL SPLIT 15 12 30 25
AT SHIPMENT
L Tot. = Total tubing length (L1 + L2 + L3...)
Ln = Maximum tubing length of a single indoor unit (n=1,2,3...)
REQUIRED AMOUNT OF ADDITIONAL REFRIGERANT
For tubing 1/4 “ - 3/8” = 15g/m
For tubing 1/4 “ - 1/2” = 20g/m
For tubing Emix (3/8”) = 15g/m
LIMIT OF ELEVATION DIFFERENCE - OUTDOOR UNIT/INDOOR UNIT: 10m (H1, H2, H3, H4,H5, H6)
LIMIT OF ELEVATION DIFFERENCE BETWEEN INDOOR UNITS: 5m (H)
No additional charge of compressor oil is necessary.