Installation Instructions

5
ADDITIONAL MATERIAL REQUIRED FOR INSTALLATION (NOT SUPPLIED)
NARROW TUBE LARGE TUBE
MODEL (INDOOR UNIT)
OUTER DIAMETER MIN. THICKNESS OUTER DIAMETER MIN. THICKNESS
A 6,35 mm 0,8 mm 9,52 mm 0,8 mm
B - C 6,35 mm 0,8 mm 12,7 mm 0,8 mm
Deoxidized annealed copper tube for refrigerant tubing connecting the units of the system; it has to be insulated with
foamed polyethylene (min. thickness 8mm).
PVC pipe for condensate drain pipe (ø int.18mm) in length suitable to let the condensate flow into the outside drainage.
Anti-freeze oil for flare connections (about 30g.).
Electric wire: use insulated copper wires of size and length as shown at paragraph “SYSTEM WIRING DIAGRAMS”.
220 - 240 V ~ 50 Hz
DELAYED FUSE
Main switch for disconnection from the supply line must have a contact separation
in all poles that provides full disconnection under category III overvoltage conditions.
Supply power wire A:
Multipolar electric wire. Size and length of the suggested electric wire are showed on table “electrical data”. The wire
must be Mod. H07RN-F (according to CEI 20-19 CENELEC HD 22). Make sure the length of the conductors between
the fixing point and the terminals allows the straining of the conductors L, N before that of the grounding.
Connecting wire B (SHIELDED):
Bipolar electric shielded wire; size and length of the suggested electric wire are showed on table “electrical data”.
The wires have not to be lighter than Mod. H05VVC4V5-K (according to CEI 20-20 CENELEC HD21).
Connecting wire C (with ground conductor):
Multipolar electric wire; size and length of the suggested electric wire are showed on table “electrical data”. The
wires have not to be lighter than Mod. H07RN-F (according to CEI 20-19 CENELEC HD22).
LENGTH, SIZE WIRES AND DELAYED FUSE
MODEL
AEI1G65EMX
mm
2
16 A
MONO SPLIT
DUAL SPLIT
EMX3PH
TRIAL SPLIT 12,5 A
20
L ("A") m
L ("B") m
L ("C") m
2,5
0,75
1,5
25
25
35
35
30
30
EG
3 INDOOR UNITS
3 PHASE
380 - 415 3N ~ 50 Hz
POWER SUPPLY
AC 380-415V
3PHASE 50Hz