Technical data

3
3 - 14
Mini Multiset Unit Specifications
1. Outdoor Unit
Outdoor unit (F)
MODEL No. AES 06 MMIH
Power source 220 - 230 - 240 V / 1N / 50 Hz
Controller P.C.B. Ass’y
Compressor
CR-CR605GXH56
Type
Control circuit fuse 250V, 6.3A
kW
MPa
Rotary (Hermetic)
INV (Inverter)
Propeller (1 ... ø460) 2
Model ... Code No.
Motor rated output
C-9RVN273H0T ... 808673805
4
Compressor oil (ETHER FV68S)
cc 1,900
Coil resistance V - U: 0.138, U - W: 0.138
W - V: 0.138
(Ambient temperature 25°C)
Safety devices
Thermal protector ON / OFF
Microprocessor safety devices
Microprocessor safety devices
Crank case heater
Yes
8 ... 250 – 800
UGBTEF – 95STS503 / 504 ... 90W
Compressor current detection circuit
Compressor discharge gas temperature control
V, W 240, 25
High pressure switch
Set pressure ON / OFF
Safety device
Model ... Nominal output
No. of pole ... r.p.m.
Heat exchanger
Coil Aluminum plate fin / Copper tube
Rows…fin pitch mm
W
3 … 1.4
Face area m
2
3.25
Fan (Number ... diameter (mm))
Fan motor