Install Instructions
10
! !
MOUNTING INSTRUCTIONS
Mount the AZ-CP Zone Valve Control vertically on a solid wall or par-
tition. For your convenience it is recommended that the control be
mounted as close as possible to the device to be controlled. The
switching relay should never be mounted more than 75 feet away.
Select a location that is easily accessible for installation and service.
NOTE: To reduce the possible transformer hum and relay noise that is sometimes am-
plied by mounting surfaces such as sheet metal, plasterboard, and similar materials,
place rubber or felt washers between the case and the mounting surface.
1. Position the control and mark the mounting holes.
2. Start screws (not provided) for the keyhole type mounting
holes in the upper corner(s). Tighten the screws down to about
⅛” (3mm) from the surface.
3. Hang the control on the screw(s), position the case, and start
the bottom screws.
4. Tighten all screws.
ELECTRICAL SPECIFICATIONS AND WIRING
WARNING
ELECTRICAL SHOCK HAZARD! Disconnect power be-
fore installing or servicing. Can cause severe personal
injury, death, or substantial property damage if ignored.
– GENERAL WIRING NOTICE –
All primary wiring must be 14 AWG minimum. Torque terminal
screws 6 to 7 inch pounds.
U.S.A. - National Electric Code and any other national, state, or
local code requirements. Wiring must be N.E.C. Class 1.
CANADA - C.S.A. C22.1 Canadian Electrical Code Part 1 and
any other national, provincial, or local code requirements. Wiring
must be C.S.A. C22.1 C.E.C. Part 1.