FIELD SELECTABLE OPTION SWITCHES
NOTE: Priority selection switches may be covered with protective lm. Remove be-
fore using selection switches.
– ZONE VALVE/PUMP SELECTION SWITCH –
Control must be in priority mode (priority switch ON) to access this
feature. With the zone valve/pump switch in the OFF position, only
the priority
ZONE VALVE terminals are energized when Zone 1
calls for heat. With the zone valve/pump switch in the ON position,
the priority PUMP terminals will be energized with 120Vac when
Zone 1 calls for heat.
IMPORTANT: A jumper wire (not included) must be installed be-
tween terminals 3 and 4 of Zone 1 when using the Priority Pump
Feature. A jumper is not required when using a zone valve.
PRIORITY SELECTION SWITCH –
If priority switch is in the ON position:
1. Zone 1 becomes priority zone.
2. When Zone 1 calls for heat, the priority zone is activated
and all other zones are deactivated. (Zone valves for Zones 2
and higher will not operate.) Priority ON light turns on.
3. Built-in timer automatically shuts off priority feature (light
off) temporarily if priority zone calls for heat longer than 30
minutes, allowing all zones to operate. Repeats every 30 min-
utes until priority zone is satised. Prevents house freeze-up
in event of indirect heater malfunction.
ZR-ZC SELECTION SWITCH –
The ZR-ZC switch is used in tankless coil boiler applications. The ZR-
ZC terminals on the AZ-CP control are connected to the ZR-ZC termi-
nals on the boiler aquastat or low limit control. If the ZR-ZC switch is in
the ON position the ZR-ZC terminals are energized when there is a call
for heat on the priority zone and the priority zone end switch is closed.