ZONE STAGING
Zone Staging is a feature that is unique to the AZ-6CP control.
When the AZ-6CP senses a power demand that exceeds the capa-
bilities of the 75VA transformers, the control will energize one zone
at a time until all calling zone valves are opened. Please note that
Priority/Zone 1 is not affected by Zone Staging and is permitted to
open at any time.
! !
! !
AZ-CP CONTROL EXPANSION
Following the instructions below, up to two (2) AZ-CP controls can
be wired together. Using two AZ-6CP controls, this allows a maxi-
mum of ten zones plus a priority zone to be installed in a system.
WARNING
Do not attempt to chain more than 2 controls together.
– INSTALLATION OF MULTIPLE CONTROLS –
1. Mount controls following directions in this instruction
manual.
2. Wire controls together as shown on next page. Note that
only the priority zone is shown wired. Other zones are in-
stalled as shown previously in this manual.
3. Move the priority selection switch to the ON position on
both controls.
WARNING
When wiring the thermostat to both controls verify that
there is no call for heat when the thermostat is not call-
ing. If there is a continuous call on the priority zone re-
gardless of the state of the thermostat, the transformers
may be out of phase. If this occurs, reverse the C & R
Transformer leads on the secondary control.
DO NOT RUN CONTROL FOR AN EXTENDED PERIOD
OF TIME WITH TRANSFORMERS OUT OF PHASE.