Installation Instructions

10
GB
For the following information:
- Maximum height between units.
- Required tools.
- Advice concerning the piping installation.
- Connection to the outdoor unit.
- Leak testing.
- Vacuum operation.
- Additional refrigerant charge.
Refer to the installation instructions provided with the outdoor unit.
For the connection to the indoor unit's flare couplings, use 2 wrenches to
maintain the coupling.
Tighten to the following tightening torque values:
- ø 1/4”: 14 - 18 N.m.
- ø 3/8”: 34 - 42 N.m.
- ø 1/2”: 49 - 61 N.m.
- ø 5/8”: 68 - 82 N.m.
- ø 3/4”: 100 - 120 N.m.
4.2 - HYDRAULIC CONNECTION
4.2.1 - WATER INLET AND OUTLET CONNECTION
Connect the water inlet and outlet lines to the corresponding
couplings.
Install the hydraulic filter (1) (supplied) on the water intake. Connect it
using 2 isolation valves (2) (not supplied) for cleaning purposes.
"Water connection hose" accessories may be used (refer to the
accessories paragraph).
4.2.2 - FILLING / DRAINAGE CONNECTION
Use the proper connection of the safety valve kit for filling or draining
water from the unit.
To use this connection, install a shut-off valve with drain tap (3) (not
supplied).
4.2.3 - SAFETY VALVE CONNECTION
• The two safety valves open if the pressure in the hydraulic system
exceeds 3 bar.
A flexible hose (4) (not supplied) can be connected to the coupling
insert (coupling OD: 18 mm) of the two valves.
Note: use the safety valve taps to complete the draining of the unit.
4.3 - ELECTRICAL CONNECTION
4.3.1 - GENERAL:
The acceptable voltage variation is: ± 10% during operation.
The electrical connection conduits must be fixed.
Use the cable clamps underneath the unit and route the wires into the electric panel, to the terminal strips.
Class 1 unit.
The electrical installation must comply with the standards and regulations applicable where the unit is being installed
(in particular NF C 15-100 IEC 364).
In case you should deactivate the hydrokit, do not disconnect the unit, but place the control unit’s knob on the symbol
(Stop), otherwise disconnect also the outdoor unit.
4.3.2 - POWER SUPPLY
The power supply must come from an isolation and electric protection device (not supplied) in accordance with existing
regulations.
• A two-pole circuit breaker (not supplied) must be installed to protect single-phase equipment or a three-pole circuit
breaker (not supplied) for three-phase equipment. See the intensity ratings table.
Note 1
:
The unit is designed to be connected to a power supply having a TT neutral regime (neutral to ground) or TN.S regime
(to neutral) as per NF C 15-100.
1
2
3
4
4