Technical information
TEMPERATURE REGULATION CONTROLLED BY THE
EXTERNAL SENSOR
PP
By pressing the and it is possible to make the following
adjustments:
“
9
9
0
0
” Temperature regulation controlled by the external sensor is
inactive (not installed).
“
9
9
1
1
” T
emperature regulation controlled by the external sensor is
activ
e (installed).
41
ADAPTING THE HEAT CURVE “
P
P
6
6
”
(Only enabled when the outdoor sensor is activated)
Should the external sensor be fitted it will be necessary to set the
heating curve (see page 41) and may be necessary to adjust the
parallel shift depending on the performance of the heating system
used.
If the temper
ature in the house is too high, it will be necessary to
decrease the parallel shift, whereas if the temperature is too low it will
be necessary to increase the parallel shift as described below.
To set up the external sensor proceed as follows;
1. Access the settings menu by pressing the and buttons
for five seconds;
2. Press the button 5 times to access Parameter 6
3.
P
P
6
6
will now appear in the left hand display
4. Adjust the parallel shift by turning the heating control knob
clockwise to increase or anti-clockwise to decrease as shown
below. The shift value can be read on the right hand display, from
-20 to +20 (Fig. 3.26).
+20
20
-20
6
60
100
-20
+20
-20 +20
to in
crea
se
the
cu
rve
in
pa
ral
lel
to
decrea
se
the
cu
rve
in
pa
ral
lel
Flo
w temper
ature (
°
C)
External temperature (°C)
FIG. 3.26
FIG. 3.25
SETTING THE TEMPERATURE FIELD
rr
Using the programming keys and it is possible to make the
f
ollowing adjustments:
“
0
0
0
0
” signifies that the flow temperature (which may be set by
means of the knob on the front control panel) may be
regulated from 20 to 75°C.
“
0
0
1
1
” s
ignifies that the flow temperature (which also may be set by
means of the knob on the front control panel) may be
regulated from 46 to 82 °C.
FIG. 3.20
FIG. 3.21