Installation and Use

46
GB
MONOSPLIT INSTALLATION MULTISPLIT INSTALLATION
1L
2N
S
W
L
N
L
(A)
N
(A)
S
(A)
L
N
3. Fasten the cables using the cable clamp.
4. Put the cover back in place, ensuring it is positioned correctly.
3.3 Connecting to the mains electricity supply
Appliance connection must adhere to European and national standards, and must be protected by a 30 mA di erential
switch. Connection to the mains must be permanent (not using a plug) and equipped with an omnipolar switch com-
plying with current CEIEN standards (contact air gap of at least 3 mm when open, preferably tted with a fuse). Proper
connection to an e cient earthing system is essential for ensuring safe operation of the device.
1. Remove the cover.
2. Connect the conductors to the screw terminals. Screw the terminal board screws tightly to avoid any loosening.
3. Fasten the cables using the cable clamp.
4. Put the cover back in place, ensuring it is positioned correctly.
MONOSPLIT INSTALLATION MULTISPLIT INSTALLATION
1L
2N
S
W
L
N
L
(A)
N
(A)
S
(A)
L
N
3.4 Connection types
MONOSPLIT INSTALLATION
External unit model Power supply Switch type
Connection
cable
Connection
cable type
Power supply
cable
Power supply
cable type
MONO UNIV 25 MD0-O
220-240 ~ 50 Hz 10 A 5G 1,5 mm
2
H07RN-F 3G 1,5 mm
2
H07RN-F
MONO UNIV 35 MD0-O
220-240 ~ 50 Hz 16 A 5G 1,5 mm
2
H07RN-F 3G 1,5 mm
2
H07RN-F
MONO UNIV 50 MD0-O
220-240 ~ 50 Hz 16 A 5G 1,5 mm
2
H07RN-F 3G 1,5 mm
2
H07RN-F
MULTISPLIT INSTALLATION
External unit model Power supply Switch type Connection cable
Connection
cable type
Power supply
cable
Power supply
cable type
DUAL 55 XD0B-O 220-240 ~ 50 Hz 20A 4G 1,5 mm
2
H07RN-F 3G 1,5 mm
2
H07RN-F
TRIAL 80 XD0B-O 220-240 ~ 50 Hz 30A 4G 1,5 mm
2
H07RN-F 3G 1,5 mm
2
H07RN-F
QUADRI 110 XD0B-O
220-240 ~ 50 Hz 30A 4G 1,5 mm
2
H07RN-F 3G 2,5 mm
2
H07RN-F
PENTA 121 XC8B-O
220-240 ~ 50 Hz 30A 4G 1,5 mm
2
H07RN-F 3G 2,5 mm
2
H07RN-F
Power supply