Installation and Use

GB
/ 45
TEMPLATE
1.3 Installing the template
NOTES:
Install the internal unit in a place free from all obstacles (such as
curtains) that could hinder the receipt of the remote control signals
and that allows for the air lters to be pulled out without causing any
inconvenience.
Install the internal unit in a position where the air
ow will not be obstructed.
WARNING:
Install the template on a solid wall that is not subjected to any
vibrations.
1. Using a mason’s level, position the template in such a way as to
ensure it is perfectly on-axis, both vertically and horizontally.
2. Fasten the template with 5 screws. Be careful not to pierce or
damage any pipes or wiring in conduits (risk of personal injury
from electrocution).
3. Then use the other screws to fasten the template to the wall uni-
formly across the entire surface.
4. Make a hole in the wall for all piping and electrical connections to
pass through.
NOTE:
- Refer to the dimensions of the template (see photo) to de ne the
optimum position for the holes. The holes should have a diameter
of at least 65 mm.
- Drill a hole in the wall that is 5-10 mm lower on the outside than it
is on the inside, so that the slope encourages downward ow of
the condensation.
1.4 Installing the internal unit
1. Push the piping, together with all cables, through the hole made
in the wall and hook the internal unit onto the top of the template.
2. Shape the piping and cables well.
3. Push the lower part of the internal unit well up against the tem-
plate.
NOTE:
Keep in mind the fact that the hooks on the template are smaller
than the cavities at the rear of the unit. This allows you to adjust the
position of the unit, with the template already secured to the wall, by
approximately 30-50 mm to the left or right, according to the model.
Make sure that:
a. The top and bottom hooks on the internal unit are securely fas-
tened onto the template.
b. The unit is fully horizontal.
If the appliance is not level, water may leak from it onto the oor.
c. The drain pipe is at the right gradient (minimum of 3 cm for each
metre in length).
d. The drain pipe stays at the bottom of the hole in the wall.
NOTES:
- Do not kink or constrict the internal unit piping in any way. Avoid bends measuring less than 10 cm in radius.
- Do not bend the same section of the pipe too often as it could kink after 3 attempts.
- Only remove the closing plugs from the internal unit piping immediately prior to making the connections.
- Keep the condensation drain pipe at the bottom of the hole in the wall, otherwise it could leak.
ø 65 mm
ø 65 mm
ø 65 mm
ø 65 mm
ø 65 mm
ø 65 mm
285 mm
117,5 mm123,6 mm
398 mm
805 mm
183,6 mm
228,5 mm 241 mm
45 mm
47 mm
47 mm
39 mm
285 mm
246 mm
506 mm
1037,5 mm
271,7 mm
316,7 mm 291 mm
45 mm
47 mm
47 mm
55 mm
302 mm
123,7 mm100,6 mm
439 mm
958,3 mm
259 mm
304 mm 224,2 mm
45 mm
47 mm
47.5 mm
36,7 mm