Installation and Use

GB
46 /
1.5 Installing the external unit
The external unit must be moved and stored in an upright position,
to ensure suitable distribution of the oil in the refrigerant circuit and
prevent damage to the compressor.
Adhere to the procedure as described, and then start connecting
the piping and electrical wiring.
- Install the external unit in a place where the noise made by the
appliance and the expelled hot air cannot be a source of incon-
venience.
- Choose a place that does not obstruct free passage and where
the condensation water produced can easily be ducted to the
outside.
- Do not install the external unit in narrow areas which limit the air
ow, or in places exposed to strong winds.
For wall installation:
- install the unit securely onto a solid wall;
- pinpoint the most suitable position on the wall, allowing enough
room for any maintenance work to be carried out easily;
- fasten the brackets to the wall using rawlplugs suitable for the
type of wall in question (take care not to damage any wiring or
piping in conduits);
- use rawlplugs which can support a weight greater than that of
the external unit: during operation the machine vibrates and
should remain installed for years without the screws becoming
loose.