Installation and Use

GB
/ 49
CONNECTION PIPING
PIPE UNIONS
LIQUID COCK
GAS COCK
4. Connect the pipes using two spanners, taking care not to damage the pip-
ing. If the tightening force is insu cient, then there may well be leaks. And
if the tightening force is excessive, then there may also be leaks as the
ange could be damaged. The safest system is constructed by tightening
the connection using a xed spanner and a dynamometric spanner: in this
case, use the table “tightening torques for ange connections”.
5. We recommend you leave an extra 50 cm of pipe for any subsequent work
carried out in the vicinity of the cocks.
2.8 Connections to the external unit
Screw the pipe unions onto the external unit connections with the same tight-
ness as for the internal unit.
To avoid leaks, pay particular attention to the following points:
- Tighten the pipe unions, taking care not to damage the piping.
- If the tightening force is insu cient, then there may well be leaks. And if the
tightening force is excessive, then there may also be leaks as the ange
could be damaged.
- The safest system is constructed by tightening the connection using a dy-
namometric spanner: in this case, use the tables below (for copper piping).
TIGHTENING TORQUES FOR FLANGE CONNECTIONS
Pipe Tightening torque
[kgf x cm]
Corresponding e ort
(using a 20 cm spanner)
6.35 mm (1/4”) 160 - 200 wrist force
9.52 mm (3/8”) 300 - 350 arm force
12.70 mm (1/2”) 500 - 550 arm force
15.88 mm (5/8”) 630 - 770 arm force
TIGHTENING TORQUE FOR PROTECTION CAPS
Tightening torque [kgf x cm]
Service connection 70-90
Protection caps 250-300
LENGTH OF THE PIPING
The maximum length for the connection piping varies depending on the mod-
el. When the length is over 5 m, take care to add the right amount of refriger-
ant per metre.
If you need to install the external and internal units with a height di erence
over 5 m ( g. B and g. C), use siphons on the gas piping in order to allow oil
to return to the compressor properly.
NOTE:
We recommend making a loop in the piping near the external unit, so as to
reduce the vibrations transmitted from that point.
IMPORTANT: CHECK FOR REFRIGERANT LEAKS
Once you have created the connections and a vacuum, open the cocks so
that the gas lls the piping and always check for leaks using a leak detector
(risk of personal injury from cold burns).
max 8 (20) m
g. B
5 m