THERMODYNAMIC PERFORMANCE OF EXTERNAL UNIT IN HEATING/COOLING MODE EN14511
PRESTAZIONI TERMODINAMICHE DELL’UNITÀ ESTERNA IN MODALITÀ RISCALDAMENTO/RAFFRESCAMENTO EN 14511
PRESTACIONES TERMODINÁMICAS DE LA UNIDAD EXTERNA EN MODO CALEFACCIÓN/REFRIGERACIÓN EN 14511
DESEMPENHO TERMODINÂMICO DA UNIDADE EXTERNA NO MODO AQUECIMENTO/ARREFECIMENTO EN 14511
ΘΕΡΜΟΥΝΑΜΙΚΕΣ ΕΠΙ∆ΟΣΕΙΣ ΤΗΣ ΕΞΩΤΕΡΙΚΗΣ ΜΟΝΑ∆ΑΣ ΣΕ ΛΕΙΤΟΥΡΓΙΑ ΘΕΡΜΑΝΣΗΣ/ΨΥΞΗΣ EN 14511
A KÜLSŐ EGYSÉG TERMODINAMIKUS TELJESÍTMÉNYE HŰTÉS/FŰTÉS ÜZEMMÓDBAN EN 14511
OSIĄGI TERMODYNAMICZNE JEDNOSTKI ZEWNĘTRZNEJ W TRYBIE OGRZEWANIA/CHŁODZENIA EN 14511
CARACTERISTICI TERMODINAMICE ALE UNITĂŢII EXTERNE ÎN MODUL DE RĂCIRE/ÎNCĂLZIRE EN 14511
TERMODINAMSKI IZKORISTKI ZUNANJE ENOTE V NAČINU OGREVANJA/HLAJENJA EN 14511
TERMODINAMIČKI UČINAK VANJSKE JEDINICE U REŽIMU GRIJANJA/HLAĐENJA EN 14511
ТЕРМОДИНАМІЧНІ ХАРАКТЕРИСТИКИ ЗОВНІШНЬОГО БЛОКУ В РЕЖИМІ ОПАЛЕННЯ / ОХОЛОДЖЕННЯ EN 14511
TERMODINAMIČKI UČINAK SPOLJAŠNJE JEDINICE U REŽIMU GREJANJA/HLAĐENJA EN 14511
ISITMA/SOĞUTMA MODUNDA DIŞ ÜNİTENİN TERMODİNAMİK PERFORMANSLARI EN 14511
ТЕРМОДИНАМИЧЕСКИЕ ХАРАКТЕРИСТИКИ НАРУЖНОГО БЛОКА В РЕЖИМЕ ОТОПЛЕНИЯ/ОХЛАЖДЕНИЯ EN 14511
TERMODYNAMICKÉ PARAMETRY EXTERNÍ JEDNOTKY EN 14511
MODEL 40 M 50 M 70 M 90 M 110 M
1 Data in heating mode: heat exchanger entering/leaving water temperature 30 °C/35 °C, outside air temperature 7 °C db/6 °C wb
2 Nominal heating capacity (HEO) kW 3,50 4,40 6,40 8,49 10,40
3 Power input kW 0,69 0,88 1,28 1,66 2,08
COP kW/kW 5,11 5,02 5,00 5,10 5,00
2 Nominal heating capacity (HPO) kW 5,90 6,70 8,70 13,6 15,0
3 Power input kW 1,28 1,49 1,93 2,96 3,33
COP kW/kW 4,60 4,50 4,50 4,60 4,50
1 Data in heating mode: heat exchanger entering/leaving water temperature 30 °C/35 °C, outside air temperature 2 °C db/1 °C wb
2 Nominal heating capacity kW 2,80 3,50 4,91 6,69 8,00
3 Power input kW 0,70 0,88 1,21 1,67 1,93
COP kW/kW 4,01 4,00 4,05 4,01 4,15
1 Data in heating mode: heat exchanger entering/leaving water temperature 30 °C/35 °C, outside air temperature -7 °C db/-8 °C wb
2 Nominal heating capacity kW 4,09 5,00 7,00 9,10 11,00
3 Power input kW 1,25 1,64 2,26 2,80 3,49
COP kW/kW 3,27 3,06 3,10 3,25 3,15
4 Data in cooling mode: heat exchanger entering/leaving water temperature 23 °C/18 °C, outside air temperature 35 °C
5 Nominal cooling capacity kW 4,80 5,87 7,50 10,55 12,50
3 Power input kW 0,90 1,20 1,50 2,17 2,74
EER kW/kW 5,35 4,89 5,00 4,86 4,56
6 Data in heating mode: heat exchanger entering/leaving water temperature 40 °C/45 °C, outside air temperature 7 °C db/6 °C wb
2 Nominal heating capacity kW 3,25 4,12 6,00 8,16 9,90
3 Power input kW 0,87 1,11 1,67 2,08 2,64
COP kW/kW 3,74 3,71 3,60 3,93 3,75
6 Data in heating mode: heat exchanger entering/leaving water temperature 40 °C/45 °C, outside air temperature 2 °C db/1 °C wb
2 Nominal heating capacity kW 2,55 3,21 4,63 6,25 7,50
3 Power input kW 0,89 1,08 1,51 2,05 2,36
COP kW/kW 2,88 2,99 3,06 3,05 3,19
6 Data in heating mode: heat exchanger entering/leaving water temperature 40 °C/45 °C, outside air temperature -7 °C db/-8 °C wb
2 Nominal heating capacity kW 3,80 4,85 6,75 8,60 10,45
3 Power input kW 1,46 1,91 2,78 3,29 4,10
COP kW/kW 2,60 2,54 2,43 2,62 2,55
7 Data in cooling mode: heat exchanger entering/leaving water temperature 12 °C/7 °C, outside air temperature 35 °C.
5 Nominal cooling capacity kW 4,00 5,05 7,20 9,05 11,00
3 Power input kW 1,17 1,60 2,29 2,87 3,75
EER kW/kW 3,42 3,16 3,14 3,15 2,93
9 Type of refrigerant R-410A
10 Compressor DC twin-rotary
11 Expansion valve PMV
12 Water connections, inlet/outlet (MPT gas) in 1
HEO - High efficiency operation
HPO - High power operation