Technical information

14
installation
Note:
The distance between the cold feed and the open
vent pipe shall be no more than 150mm.
The cold feed must be inverted as shown.
The open vent pipe must be a minimum of 22mm
diameter.
The cold feed pipe must be a minimum of 15mm
diameter.
The cold feed and open vent pipes must rise
continuously and be unrestricted.
The minimum distance from the top of the boiler
to the bottom of the F & E tank shall be no less
than 2m. Whilst the maximum distance shall be
not more than 27m.
The distance between the bottom of the F & E
tank and the highest point of the open vent must
be no less than 500mm.
The ow and return pipes from the boiler must
rise continuously and be unrestricted.
The supply of water to the F & E tank should be
taken from the mains water supply via a suitable
oat operated valve. While the supply from the F
& E tank to the boiler/heating circuit (via the cold
feed) shall be unrestricted.
The F & E tank must be adequately supported
and installed in accordance with relevant Building
Regulations.
Pump specication
The pump should be tted on the ow pipe from
the boiler and have isolating valves each side. A
variable duty pump should be set to give a tempe-
rature dierential of no greater than 20ºC.
Draining tap
A draining tap must be provided at all the lowest
points of the system which will allow the entire
system to be drained. A drain tap must also be
installed on the ow and return pipes immediately
above the boiler to ensure complete draining of the
primary ow and return is possible.
Drain taps shall be to the current standard of BS
2879.
Sealed water systems
A sealed system kit is available from Ariston. Installa-
tion instructions are supplied with the kit.
mWH
l/h
0
100
200
300
400 500 600 700 800 900
1000 1100
1200
1300
1400
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
4.5
5.0
12-18 kW
12 kW
18 kW
821 l/h = 20 Δ @ 19.1 kW
555 l/h = 20 Δ @ 12.9 kW
1.3 mWH
2.65 mWH
24 kW
1118 l/h = 20 Δ @ 26.0 kW
3.7 mWH
Pressure Loss Graphs through the boilers