Operating instructions
12
Fitting the Coaxial Flue (Horizontal)
(For Telscopic Instructions see page 13 and for Vertical Flue and
Twin Pipe Instructions see page 14)
C
ONTENTS:
1X SILICONE O-RING (60mm)
1X ELBOW (90
O
)
2
X WALL SEALS (INTERNAL &EXTERNAL)
1X ALUMINIUM FLUE PIPE INCLUDING TERMINAL (1 METRE - 60/100)
2X FLUE CLAMPS
8X SCREWS
2X SEALS
Once the boiler has been positioned on the wall, insert the elbow
into the socket (FIG 6.8) and rotate to the required position. NOTE:
It is possible to rotate the elbow 360
o
on its vertical axis.
Using the flue clamps , seals and scre ws supplied (FIG 6.8)
secure the elbow to the boiler.
The 1 metre horizontal flue kit (705958) supplied is suitable for an
exact X dimension of 823mm, and the 750mm horizontal
flue kit
(705785) is suitable for an exact X dimension of 573mm.
Measure the distance from the f ace of the e xternal wall to the
Installation
6.9 Flue Connections
FLUE SYSTEM
The provision for satisfactory flue ter mination must be made in
accordance with BS 5440-1.
The appliance must be installed so that the flue ter minal is exposed
to outside air.
The terminal must not discharge into another room or space such
as an outhouse or lean-to.
It is important that the position of the ter minal allows a free pas-
sage of air across it at all times .
The terminal should be located with due regard f or the damage
or discolouration that might occur on b uildings in the vicinity and
consideration must be given to adjacent boundaries.
In cold or humid w eather water vapour may condense on lea ving the
flue terminal. The effect of such “pluming” must be considered.
If the ter minal is less than 2 metres abo ve a balcon y, above
ground or above a flat roof to which people ha ve access, then a
suitable terminal guard must be fitted. When ordering a terminal
guard, quote the appliance model number.
A suitable terminal guard is available from:
TOWER FLUE COMPONENTS
Morley
Road
Tonbridge
Kent TN9 1RA
The minimum acceptable spacing from the ter minal to obstr uc-
tions and ventilation openings are specified in F
IG. 6.7.
IMPORTANT!
For all flue systems, a restrictor may need to be insert-
ed into the exhaust manifold, the size of the restrictor
and details of fitting requirements are sho wn in Table
6.1 (Page 18).
T
ERMINAL
P
OSITION
mm
A - Directly below an openable window
or other opening300
B - Below gutters, solid pipes or drain pipes 75
C - Below eaves 200
D - Below balconies or car-port roof 200
E - From vertical drain pipes and soil pipes 150
F - From internal or external corners 300
G - Above ground or balcony level 300
H - From a surface facing a terminal 600
I - From a terminal facing a terminal 1200
J - From an opening in the car por t
(e.g. door, window) into dwelling 1200
K - Vertically from a terminal in the same wall 1500
L - Horizontally from a terminal in the same wall 300
M - Horizontally from an opening window 300
N - Fixed by vertical flue terminal
FIG. 6.7
FU010ARev1
NOTE: THE FLUE MUST NOT TERMINATE IN A PLACE LIKELY TO CAUSE
NUISANCE
Ø 60/100 mm
FIG. 6.8
FU003A