Installation and operating instructions E.2 Series mechanical seal replacement File No: 10.
contents 1.0 Existing pump removal from 4 system piping 2 .
i nstall a ti o n & o perat i ng i nstr uct i on s e.2 Series mechanical seal replacement 4 1.0 existing pump removal from system piping (leaving the volute in place) 1 Ensure that electric power is disconnected and locked out. Loosen the screw from the terminal box cover and remove the cover. Disconnect the supply wires from the circulator only, leaving the capacitor wires connected.
e.2 Series mechanical seal replacement in sta lla t io n & oper ating in struct io n s 5 15 Remove the installation tool from the shaft. 16 Install the impeller keeping the inlet end up. Make sure to align the flats to the shaft flats and push the impeller down tightly to the seal. 17 Place 2-3 drops of medium strength thread locker liquid on the nut threads. 18 Install the special left hand thread nut on the motor shaft.
toronto 23 bertrand avenue toronto, ontario canada m1l 2p3 +416 755 2291 buffalo 93 east avenue north tonawanda, new york u.s.a. 14120 -6594 +716 693 8813 birmingham heywood wharf, mucklow hill halesowen, west midlands united kingdom b62 8dj +44 (0) 8444 145 145 manchester wenlock way manchester united kingdom m12 5jl +44 (0) 8444 145 145 bangalore #59, first floor, 3rd main margosa road, malleswaram bangalore, india 560 003 +91 (0) 80 4906 3555 shanghai no.