DT-203X, DT-105X and DT-110X display series 
4.4.3. Omron protocol. 
Omron  protocol  supports  two  kinds  of  messages.  Messages  with  and  without 
variables.With this protocol the display may control as many as 6 messages without variables 
and 4 messages with variables together. All messages are shown sequentially. 
To know what message should be shown, the display reads a table of 18 DM’s from the 
PLC  memory.  The  first  DM  number  must  be  configured  into  the  DM  parameter.  This 
parameter is specific for this protocol. 
The OMRON Hostlink protocol does not work with RS-485, but with RS-422. 
The next table shows the meaning of each DM 
DM Number 
DM n 
Number of Message without variables 1 
DM n+1 
Number of Message without variables 2 
DM n+2 
Number of Message without variables 3 
DM n+3 
Number of Message without variables 4 
DM n+4 
Number of Message without variables 5 
DM n+5 
Number of Message without variables 6 
DM n+6 
Number of Message with variables 1 
DM n+7 
Number of Message with variables 2 
DM n+8 
Number of Message with variables 3 
DM n+9 
Number of Message with variables 4 
DM n+10 
Number of DM where variable 1 is located 
DM n+11 
Total number of DM's of variable 1 
DM n+12 
Number of DM where variable 2 is located 
DM n+13 
Total number of DM's of variable 2 
DM n+14 
Number of DM where variable 3 is located 
DM n+15 
Total number of DM's of variable 3 
DM n+16 
Number of DM where variable 4 is located 
DM n+17 
Total number of DM's of variable 4 
4.4.3.1. Set a message without variables. 
When you want  to set a  message without variables, you should  put the Message 
Number into a free place on the DM table, between positions DM n and DM n+5. If more than 
one message is set, the position into the table is used to control the order in which messages 
will be displayed. 
4.4.3.2. Reset a message without variables. 
To reset messages  without  variables,  you must set  its position  on the  table  to  0 
orchange the message number for the other message number. To display the message 15, the 
DM must be 15 in BCD 
Examples: 
DM parameter = 108 
DM parameter = 2145 
DM parameter = 1 
DM 108 
0 
DN 2145 
4 
DM 1 
2 
DM 109 
0 
DM 2146 
0 
DM 2 
6 
DM110 
15 
DM 2147 
0 
DM 3 
0 
DM 111 
0 
DM 2148 
156 
DM 4 
0 
DM 112 
0 
DM 2149 
0 
DM 5 
0 
DM 113 
0 
DM 2150 
0 
DM 6 
24 
Message 15 ON 
Meesages 4 and 156 ON 
Messages 2, 6 and 24 ON 