Submittal Sheet

4
2/2
SERIES
8040
Features
2-way normally closed operation
For gas pilot control of commercial and industrial
gas burners
Direct lift with resilient soft seating for tight shut-off
Valves provided with 1/8" NPT downstream pipe tap
with plug for routine testing
Mountable in any position
Direct Acting
Gas Shutoff Valves
1/8" to 3/8" NPT
NC
Solenoid Enclosures
278144-SV311-2D
Approvals
UL listed to standard 429 “Electrically Operated
Valves,” Guide YIOZ, File MP618 Safety Valves.
FM Approved to Class 7400 “Liquid and Gas Safety
Shutoff Valves.”
CSA Certified to:
1) Standard C22.2 No. 139 “Electrically Operated
Valves,” File 010381.
2) Automatic Gas Valves Z21.21 (6.5), File 112872.
3) Automatic Gas Safety Shutoff Valves C/I (3.9),
File 112872.
Standard: Watertight, Types 1, 2, 3, 3S, 4, and 4X with 1/2" conduit hub.
Optional: RedHat II - Explosionproof and Watertight. To order, add Prefix “EF” to
catalog numbers. (e.g. EF8040H006)
Construction
COMBUSTION
307
Valve Parts in Contact with Fluids
Body Aluminum
Seals and Disc NBR
Core Tube 305 Stainless Steel
Core and Plugnut 430F Stainless Steel
Springs 17-7 PH
Shading Coil Copper
Pipe Plug Zinc Plated Steel
Standard
Coil and
Class of
Insulation
Watt Rating and
Power Consumption
Ambient
Temp.°F
Spare Coil Family
AC General Purpose Explosionproof
Watts
VA
Holding
VA
Inrush AC AC
F 6.1 16 40 -40 to 125 238210 238214
H 6.1 16 40 -40 to 140 238410 238414
Standard Voltages: 24, 120, 240 volts AC, 60 Hz (or 110, 220 volts AC, 50 Hz).
Optional High Ambient Temp: 140˚F Class H coil with prefix HT.
Electrical
^ #
Valve Response Time
Opening Time: Less than 1 second
Closing Time: Less than 1 second
Fluid
Fuel Gas