Submittal Sheet

COMBUSTION
311
4
2/2
SERIES
8214
Features
2-way normally closed operation
Unique double disc design with overtravel provides
redundant sealing for leak tight shutoff
Die-cast aluminum bodies
Zero differential piloted diaphragm
For on-off control of fuel gas in commercial and
industrial gas burners
Valves provided with 1/8" NPT upstream and
downstream pipe taps with plugs for routine testing
Watertight Enclosure
Gas Shutoff Valves
3/8" to 2" NPT
NC
Solenoid Enclosures
Approvals
UL listed to standard 429 “Electrically Operated Valves,”
Guide YIOZ, File MP618 Safety Shutoff Valves.
FM Approved to Class 7400 “liquid and gas safety
shutoff valves.”
CSA Certified to:
1) Standard C22.2 No. 139 “Electrically Operated
Valves,” File 010381.
2) Automatic Gas Valves Z21.21 (6.5), File 112872.
3) Automatic Gas Safety Shutoff Valves C/I (3.9),
File 112872.
RedHat II molded epoxy Type 1, 2, 3, 3S, 4 and 4X combination.
General Purpose and Watertight solenoid enclosures with
1/2" conduit hub as standard.
Valve Parts in Contact with Fluids
Body Aluminum
Seals and Disc NBR
Core Tube 305 Stainless Steel
Core Guide Acetal (20.1 watt only)
Rider Ring PTFE (20.1 watt only)
Core and Plugnut 430F Stainless Steel
Springs 302 Stainless Steel
Shading Coil Copper
Pipe Plug Zinc-Plated Steel
Standard
Coil and
Class of
Insulation
Watt Rating and
Power Consumption
Ambient
Temp.°F
Spare Coil Family
DC
Watts
AC General Purpose Explosionproof
Watts
VA
Holding
VA
Inrush AC DC AC DC
F - 17.1 40 93 -40 to 125 238610 - - -
F - 20.1 48 240 -40 to 125 272610 - - -
F 22.6 - - - -40 to 104 - 238710 - -
Standard Voltages: 24, 120, 240 volts AC, 60 Hz (or 110, 220 volts AC, 50 Hz) (238610); 120,
240 volts AC, 60 Hz (272610); 12, 24 volts DC.
Construction
Electrical
^ #
Valve Response Time
Opening Time: Less than 1 second; Closing Time: Less than 1 second