Submittal Sheet

4
2/2
SERIES
8040
8215
2-WAY
Features
Lightweight, low-cost valves for air service
Ideal for low pressure applications
Provides high flow, Cv up to 138 (Kv 118)
Air and vacuum service
Direct Acting or Piloted
Aluminum Body Solenoid Valves
1/8" to 3" NPT
NC
NO
Solenoid Enclosures
Approvals:
CSA certified to:
8040 Series:
1) Standard C22.2 No. 139 "Electrically Operated
Valves," File 10381.
2) Automatic Gas Valves Z21.21 (6.5), File 112872.
3) Automatic Gas Safety Shutoff Valves C/I (3.9),
File 112872.
8215 Series Normally Closed:
1) Standard C22.2 No. 139 "Electrically Operated
Valves," File 10381.
2) Automatic Gas Valves Z21.21 (6.5), File 112872.
8215 Series Normally Open:
1) Standard C22.2 No. 139 "Electrically Operated
Valves," File 10381.
UL listed, as indicated. FM approved (Normally Closed
only, except Catalog Numbers 8215A090 and 8215A040).
RedHat II meets applicable CE directives.
Refer to Engineering Section for details.
Standard: RedHat II - Watertight, Types 1, 2, 3, 3S, 4, and 4X; RedHat - Type I.
Optional: RedHat II - Explosionproof and Watertight, Types 3, 3S, 4, 4X, 6,
6P, 7, and 9; RedHat - Explosionproof and Raintight, Types 3, 7, and 9.
(Except EF8215A40 and EF8215A90, which are suitable for Types 3 and 7
(C and D) only and have a T2B temperature rating code.)
To order, add prefix “EF” to catalog number.
See Optional Features Section for other available options.
8040
Valve Parts in Contact with Fluids
Body Aluminum
Seals, Diaphragms, Disc NBR
Disc-Holder PA (10.1 and 11.6 watt Normally Open only)
Core Guide CA
Core Tube 305 Stainless Steel
Rider Rings PTFE
Core and Plugnut 430F Stainless Steel
Springs* 302 Stainless Steel
Shading Coil Copper
* For 8040H006, 8040H007, 8040H008, spring material is 17-7 PH
Standard
Coil and
Class of
Insulation
Watt Rating and Power
Consumption
Spare Coil Part No.
DC
Watts
AC General Purpose Explosionproof
Watts
VA
Holding
VA
Inrush
AC DC AC DC
F - 6.1 16 40 238210 - 238214 -
F 11.6 10.1 25 70 238610 238710 238614 238714
B 14.9 - - - - 62691 - -
F - 15.4 27 160 99257 - 99257 -
F - 28.2 50 385 206409 - 206409 -
Standard Voltages: 24, 120, 240, 480 volts AC, 60 Hz (or 110, 220 volts AC, 50 Hz),
6, 12, 24, 120, 240 volts DC. Must be specified when ordering.
Other voltages available when required.
Electrical
Nominal Ambient Temp. Ranges
% ^ # )
7
Construction
Series
AC DC
RedHat II/RedHat RedHat II RedHat
8040
-40˚F to 125˚F
(-40˚C to 52˚C)
- -
8215
32˚F to 125˚F
(0˚C to 52˚C)
32˚F to 104˚F
(0˚C to 40˚C)
32˚F to 77˚F
(0˚C to 25˚C)
(104˚F/40˚C occasionally)
Refer to Engineering Section for details.