Submittal Sheet

4
2/2
SERIES
K3A4
COMBUSTION
Features
2-way normally closed operation
Die-cast aluminum bodies
For positive shutoff on pilot or main gas lines of
commercial and industrial gas burners
Valves provided with 1/8" NPT upstream and
dowstream pipe tap with plug for routine testing
Suitable for ambient temperatures up to 175˚F
Low Pressure Direct Acting
Gas Shutoff Valves
3/8" to 1" NPT
NC
Valve Response Time
Electrical
Opening Time: Less than 1 second
Closing Time: Less than 1 second
Solenoid Enclosures
Standard: Type 1 General Purpose Junction Box Housing with two
7/8" knock-outs.
365
Approvals
UL listed to standard 429 “Electrically Operated Valves,”
Guide YIOZ, File MP932 Safety Valves.
FM Approved to Class 7400 “Liquid and Gas Safety
Shutoff Valves” (3/8" thru 3/4" only).
CSA Certified to:
1) Standard C22.2 No. 139 “Electrically Operated
Valves,” File 113070.
2) Automatic Gas Valves Z21.21 (6.5), File 109157
and 113070
2) Automatic Gas Safety Shutoff Valves C/I (3.9),
File 113070
Valve Parts in Contact with Fluids
Body Aluminum
Seals and Disc NBR
Washer 302 Stainless Steel
Core Tube 305 Stainless Steel
Core and Plugnut 430F Stainless Steel
Core Guide CA
Springs 302F Stainless Steel
Shading Coil Copper
Body Gasket Cork
Pipe Plug Zinc-Plated Steel
Construction
Standard
Coil and
Class of
Insulation
Watt Rating and
Power Consumption
Ambient
Temp.°F
Spare Coil Family
AC General Purpose Explosionproof
Watts
VA
Holding
VA
Inrush AC AC
F 10.5 23 55 -40 to 175 064982 -
Standard Voltages: 120 volts AC, 60 Hz (or 110 volts AC, 50 Hz).
Optional Voltages: 24, 240 volts AC, 60 Hz (or 220 volts AC, 50 Hz)
K3A catalog number includes codification for voltage. However, voltage must
be specified when ordering spare coil.
^ #
Fluid
Fuel Gas

Summary of content (2 pages)