Submittal

COMBUSTION
337
4
2/2
SERIES
8214
(200)
Features
Unique double disc design with overtravel provides
redundant sealing for leak tight shutoff
Visual indication of open and shut position (Suffix “VI” & “C”)
Proof of closure switch 1 amp & visual indicator (Suffix “C”)
Silicon-free construction (Suffix “SF”)
For on-off control of fuel gas in commercial and
industrial gas burners
1/8" NPT pipe taps with plugs for routine testing
Optional flange adapters for ease of installation and service
General Purpose & Watertight Enclosure
Gas Shutoff Valves
Visual Indication & Proof of Closure (Optional)
3/4" to 3" NPT
NC
Solenoid Enclosures
Approvals
UL listed to standard 429 “Electrically Operated Valves,”
Guide YIOZ, File MP618 Safety Shutoff Valves.
FM Approved to Class 7400 “liquid and gas safety
shutoff valves.” (Suffix VI and C only)
CSA Certified to:
1) Standard C22.2 No. 139 “Electrically Operated
Valves,” File 010381.
2) Automatic Gas Valves Z21.21 (6.5), C/I, File 112872.
3) Automatic Gas Safety Shutoff Valves (3.9),
File 112872.
General Purpose: RedHat metal Type 1 General Purpose housing has a 7/8"
diameter hole to accept standard conduit hubs or connectors.
Add prefix JB to catalog number for a Junction Box construction with two
7/8" diameter knock-outs. (i.e. JB8214 265)
Watertight: RedHat II molded epoxy Type 1, 2, 3, 3S, 4 and 4X combination.
General Purpose and Watertight solenoid enclosures with 1/2" conduit
hub as standard.
Add prefix JKP to Watertight catalog number for a Watertight Junction Box.
(i.e. JKP8214G266)
^ #
Valve Response Time
Opening Time: Less than 1 second
Closing Time: Less than 1 second
Fluid
Fuel Gas
Valve Parts in Contact with Fluids
Body Aluminum
Seals and Disc NBR
Core Tube 305 Stainless Steel
Core Guide POM
Rider Ring PTFE
Core and Plugnut 430F Stainless Steel
Springs 302 Stainless Steel
Shading Coil Copper
Pipe Plug Zinc-Plated Steel
Standard
Coil and
Class of
Insulation
Watt Rating and
Power Consumption
Ambient
Temp.°F
Spare Coil Family
DC
Watts
AC General Purpose
Watts
VA
Holding
VA
Inrush AC DC
General
Purpose
F 35.1 20 43 240 -40 to 125 099257 206410
H 35.1 ----40 to 132 - 236825
H - 20 43 240 -40 to 140 222345 -
Watertight
F 15.8 20.1 48 240 -40 to 125 272610 501695
H 15.8 20.1 48 240 -40 to 140 272810 440162
Standard Voltages: 24, 120, 240 volts AC, 60 Hz (or 110, 220 volts AC, 50 Hz) 12, 24 volts DC.
Optional High Ambient Temp: 140˚F Class H coil with prefix HB (3/4" to 2" AC only),
140˚F Class H coil with prefix HT (3/4" to 2" DC only)
132˚F Class H coil with prefix HB (2" High flow to 3" DC Only)
Construction
Electrical
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com