User's Manual
Table Of Contents
- Contents
- 1 Introduction
- 2 Practical Engineering Parameters
- 3 System LAN Cabling
- 4 System Power
- 5 Control Equipment
- 5.1 Preparation
- 5.2 Room Controller (NIRC3)
- 5.3 Preparing the Room Bus and Power Cables
- 5.4 Voice Piggy Back (NIVP)
- 5.5 Connection Terminals
- 5.6 Connecting the IP Room Controller Printed Circuit Board
- 5.7 LED Lamp Boards (NILD2)
- 5.8 Corridor Lamp (NICL2)
- 5.8.1 Installing the Corridor Lamp
- 5.8.2 Removing the Corridor Lamp Printed Circuit Board
- 5.8.3 Corridor Lamp Housing
- 5.8.4 NICL2 - Corridor Lamp Electrical Connections
- 5.8.5 4-Pole Connector Terminal
- 5.8.6 Connecting the Corridor Lamp Printed Circuit Board
- 5.8.7 LED Lamp Boards for the Corridor Lamp
- 5.8.8 Connecting the LED Lamp Boards
- 5.8.9 External Corridor Lamp Inputs
- 5.9 System Manager (NISM2)
- 6 Peripherals
- 6.1 Preparation
- 6.2 Installation Instructions
- 6.3 Backplates and Surface Mounting Spacer
- 6.4 Switch Module Electrical Connections
- 6.4.1 4-Pole Connector Terminal
- 6.4.2 Preparing the Wires for the 4-pole Connector Terminal
- 6.4.3 Connecting the wire in the 4-pole Connector Terminal
- 6.4.4 4-Pole Connector Terminal with Looped Wiring
- 6.4.5 Disconnecting a Wire from the Connector Terminal
- 6.4.6 Mounting the Switch Module to the Backplate
- 6.4.7 Mounting the Switch Module to the Surface Mounting Spacer
- 6.4.8 Dismantling the Switch Modules
- 6.4.9 Dismantling a Switch Module from a Spacer
- 6.4.10 Dip Switch Settings
- 6.5 Bedside Module (NIBM2)
- 6.6 Medical Rail Socket (NIMS2)
- 6.7 Door Side Module (NIDM)
- 6.8 Pull Cord Module - Active (NIPC-W3A)
- 6.9 Toilet Cancel Module - Active (NITC-XXA)
- 6.10 Pull Cord Module - Passive (NIPC-XXP)
- 6.11 Toilet Cancel Module - Passive (NITC-XXP)
- 6.12 Pull Cord Module (NIPC2) Active and Passive
- 6.12.1 Mounting the NIPC2 Pull Cord Module
- 6.12.2 Positioning the Back box for the Pull Cord Module
- 6.12.3 NIPC2 Back plate
- 6.12.4 Mounting the NIPC2 Backplate
- 6.12.5 Drilling the Backplate Mounting Holes
- 6.12.6 Mounting the Backplate on the Wall
- 6.12.7 Preparing the Cable for the Pull Cord Module
- 6.12.8 Room Bus Electrical Connections
- 6.12.9 Room Bus Address DIP Switch Settings
- 6.12.10 Passive Pull Cord Module Electrical Connections
- 6.12.11 Mounting the NIPC2 Pull Cord Module to the Backplate
- 6.12.12 Assembling and Attaching the Pull Cord
- 6.13 Duty Selector (NIDS)
- 6.14 Card Reader (NICR)
- 6.15 Speech Module (NISP)
- 6.16 Room Display (NIRD)
- 6.17 Television Interface Module
- 6.18 Sunblind Control Module
- 7 External Inputs
- 8 Wireless Functionality
- 8.1 General
- 8.2 Principle of the teleCARE IP with Wireless Functionality
- 8.3 teleCARE Wireless with Speech
- 8.4 teleCARE IP Wireless Planning
- 8.5 Wireless Infrastructure
- 8.6 Principle of the Wireless Infrastructure
- 8.7 teleCARE IP Wireless Components
- 8.7.1 NUREP Wireless Repeater
- 8.7.2 Outdoor Box
- 8.7.3 Wireless Gateway
- 8.7.4 NUWBM3 Wireless Active Bedside Module
- 8.7.5 NIRX teleCARE IP Transceiver
- 8.7.6 Connecting the Transceiver Module
- 8.7.7 NIVP Voice Piggyback Module
- 8.7.8 NIFX Fixed Transceiver
- 8.7.9 NITX Mobile Transceiver
- 8.7.10 NUUTX Universal Transceiver
- 8.7.11 NUWIR Wireless PIR Module
- 8.7.12 IR Range Test
- 8.7.13 NUUTX NUWIR Battery Placement
- 8.7.14 (3) Slide the battery lid back into place until it snap fits.NUUTX NUWIR Mounting Instructions
- 8.7.15 NILF Low Frequency Beacon
- 8.7.6 NILF Electrical Connections
- 8.7.7 NILF DIP Switch Settings
- 8.7.8 NILF Power Supply
- 9 Installation Examples
- 9.1 2-Bed Room with Active Toilet Cancel and Active Pull Cord Peripherals
- 9.2 2-Bed Room with Passive Toilet Cancel and Passive Pull Cord Peripherals
- 9.3 2-Bed Room with a Medical Rail Socket at each Bed
- 9.4 Room Controller with Corridor Lamps (Master/Slave)
- 9.5 4-Bed Room with Speech
- 9.6 Duty Selector at a staff Station
- 9.7 Positioning of the teleCARE IP Peripherals
- Document History
TD 93021US
17 July 2017 / Ver. PF3 6
Installation Guide
teleCARE IP
3 System LAN Cabling
3.1 Ethernet Switch
The 8-port Ethernet Switch, Ascom part number APS5001, shall be used with the teleCARE IP system and
can be purchased through Ascom.
WARNING: Use of any Ethernet Switch other than Ascom part number APS5001 violates the UL
2560 listing.
3.1.1 Ethernet Switch DIN Rail Mounting
The Ethernet Switch shall be mounted on a 1.5in (35mm) DIN-rail, which can be mounted on a wall. See
instructions inside the Ethernet Switch Installation Guide provided with the switch.
3.1.2 Ethernet Switch 19” Rack and Cabinet Mounting
The Ethernet Switch can be mounted into a 19in (483mm) rack secured to a DIN Rail, which must be
attached with screws or other fixtures to the rack and must not be easily movable.
3.1.3 Ethernet Switch Installation – Seismic
For installations requiring seismic considerations, refer to OSHPD Installation Requirements and
Instructions, document number 3101998, for selection, sourcing, and installation of racks and cabinets.
After the racks or cabinets are installed, the Ethernet Switch can then be installed into a cabinet or rack,
in accordance with the instructions described in 3.1.2.
WARNING:
• Use only the cabinets or rack listed in the OSHPD Installation Requirements and Instructions
document (P/N 3101998).
• Do not use the uninterruptible power supplies described in the OSHPD installation document. The
battery backup for the teleCARE IP system must be provided by the power supply described in
section 4.2, 24Vdc / 8 Amp Power Supply (Seismic).
• Use the rack mounting accessories described in section 3.1.2 to mount the Ethernet switch to the
rack or cabinet.
• Do not apply the OSHPD Label to the rack, cabinet or, Ethernet Switch. If an OSHPD label is
required, contact your Ascom Sales Representative.
3.1.4 Ethernet Switch Power
The Ethernet Switch must be powered by the 24Vdc / 3 Amp Power Supply Ascom model APS5000
described in Section 4 of this manual. The power conductors must be in accordance with the
requirements specified in section 4.4 and connected to the four-pin removable keyed connector provided
with the unit. Power connections to the Ethernet Switch shall be in accordance with the Figure 2.
Figure 2. Ethernet Switch Power Connection