4 System Power
The teleCARE IP system power supply shall be sourced from an external 24Vdc power supply, utilizing
a dedicated 2-wire power distribution bus. The external power requirement for teleCARE IP is 24Vdc,
with an acceptable range of 21.6Vdc to 26.4Vdc.
WARNING: Use of any Power Supply other than those which are specified in this manual violates
the UL 2560 listing.
4.1 24Vdc / 3 Amp Power Supply (Standard)
The 24Vdc / 3 Amp Power Supply, Ascom part number APS5000, must be used with the teleCARE IP
system and can be purchased through Ascom.
The teleCARE IP Standard Power Supply shall be used to power the teleCARE IP system. This power
supply converts 115Vac / 60Hz input power to a 24Vdc / 3 Amp, Class 2 Rated regulated output.
There is a built-in charger to charge sealed lead acid batteries. The batteries provide the Secondary
Power to the teleCARE IP system in the event of mains AC power failure. There is an automatic
switchover to the batteries when input AC power fails. During switchover, there is zero voltage drop at
the power output. The power output fuse is rated at 15A/32Vdc.