System Description

TD 93025US
9 May 2019 / Ver. I 42
System Description
teleCARE IP
Figure 38. Connector pin designation.
7.4.3 Configurable parameters
The configuration manager (NISM2) is used to configure the functionality of the inputs. The inputs can
be configured independent from each other. The following parameters are configurable:
Jitter suppression:
Input fluctuations of contacts that open and close within a given time period generate one signal.
This can be used for PIR detectors that do not filter the movement signals. Or it can be used to
filter movements in the bed on bed sensors.
Delay time:
When the input is still present after the given time generates a signal. This is used to prevent
transient inputs to generate a signal.
Duration time:
After the input deactivates, the signal is extended. This can be used to extend a (door) button press
to generate a longer (door bell) signal.
Name/description of the notification
7.4.4 System limitations
The Configuration Manager (NISM2) supports up to 4 inputs per room (location).
The Configuration Manager supports Resident Profiles. A Resident Profile defines what sensors and
parameters are used. This simplifies the configuration process for a system. Up to 16 Resident Profiles
can be defined.
7.5 Fixed external input switch modules
The NIBM2 and NIPC-xxA switch modules are capable of handling one external input, using IN0/+V of
the NICB. The second input cannot be used and must remain open. These switch modules detect the
NICB by the inactive IN1 contact. If IN1 is used, these switch modules will not recognize the NICB
correctly and the software will interpret this as if the NISE (socket extension module) is present.
The NIDM, NITC-xxA, and NIRD switch modules are capable of handling two external inputs. The
inputs can be configured independently.