Temperature Controller 1/ 16 DIN - 48 x 48 ASCON spa ISO 9001 C e r t i f i e d M3 line c User manual • M.I.U.M3 -4/03.01 • Cod. J30-478-1AM3 IE C UL LISTED ASCON spa 20021 Bollate (Milano) Italy via Falzarego, 9/11 Tel. +39 02 333 371 Fax +39 02 350 4243 http://www.ascon.it e-mail sales@ascon.
Temperature Controller 1/ 16 DIN - 48 x 48 c M3 line C UL LISTED 3 1 2 3 274.8 RUN 275.
Information c NOTES ON ELECTRIC SAFETY AND ELECTROMAGNETIC COMPATIBILITY. Please, read carefully these instructions before proceeding with the installation of the controller. Class II instrument, real panel mounting.
Table of contents TABLE OF CONTENTS 1 2 3 4 5 6 7 INSTALLATION .............................................................................................................................Page ELECTRICAL CONNECTIONS.......................................................................................Page PRODUCT CODING ................................................................................................................Page OPERATIONS............................................................
1 - Installation 1 INSTALLATION Installation must only be carried out by qualified personnel. 1.1 GENERAL DESCRIPTION IP 20 Termination Unit EN61010 - 1 (IEC1010 - 1) Before proceeding with the installation of this controller, follow the instructions illustrated in this manual and, particularly the installation precautions marked with the B symbol, related to the European Community directive on electrical protection and electromagnetic compatibility.
1 - Installation 1.2 DIMENSIONAL DETAILS 1.3 PANEL CUT-OUT 48 mm 1.89 in 65 mm min 2.56 in min 45+0.6 mm 1.78+0.023 in 20 mm max 0.79 in max 65 mm min 2.56 in min 48 mm 1.89 in 45+0.6 mm 1.78+0.023 in 120 mm 4.
1 - Installation B 1.
1 - Installation 1.5 PANEL MOUNTING [1] 1.5.1 INSERT THE INSTRUMENT 1.5.2 INSTALLATION SECURING 1.5.3 CLAMPS REMOVING 1 Prepare panel cut-out 2 Check front panel gasket position 3 Insert the instrument through the cut-out 1 1 Fit the mounting clamps 2 Push the mounting clamps towards the panel surface to secure the instrument 1 Insert the screwdriver in the clips of the clamps 2 Rotate the screwdriver 1 2 1 2 3 1 2 B 1.5.
2 - Electrical connections 2 8 TC mA mV NO 3 9 C 4 10 B 5 11 b 6 12 A 14 C 15 NO 16 C 17 7 13 OP3 N 13 NO 1 2 8 14 3 9 15 4 10 16 5 11 17 TA 1 7 OP1 L B 2.1 TERMINATION UNIT [1] OP2-R ELECTRICAL CONNECTIONS OP2-L 18V RS485 OUT (OP4) 2 0,5 Nm Rear terminal cover 18 5.7 mm 0.22 in RTD 6 12 18 Cable size 1 mm2 18 AWG 18 screw terminals Terminals Option terminals Holding screw 0.5 Nm UL note [1] Use 60/70 °C copper (Cu) conductor only.
2 - Electrical connections PRECAUTIONS B Despite the fact that the instrument has been designed to work in an harsh and noisy environmental (level IV of the industrial standard IEC 801-4), it is recommended to follow the following suggestions. 2.2 PRECAUTIONS AND ADVISED CONDUCTOR COURSE B Conduit for supply and output cables B A B BB A B A All the wiring must comply with the local regulations. The supply wiring should be routed away from the power cables.
2 - Electrical connections 2.3 EXAMPLE OF WIRING DIAGRAM (HEAT COOL CONTROL) Power supply V~ Supervision Retransmission Power supply [3] switch RS485 RX/TX 0P4 4…20mA Cooling V~ Fuse [5] PTC [4] 1 7 V~ Fuse [5] [6] 13 OP3 2 8 14 3 18V 9 15 OP2 OP1 4 10 5 11 17 6 12 18 TC V~ Heating 10 Fuse 2A~T [6] V~ 16 OP2 CT Current transformer 50 mA [6] Allarm B Notes: 1] Make sure that the power supply voltage is the same indicated on the instrument.
2 - Electrical connections 2.3.1 POWER SUPPLY B Switching power supply with multiple isolation and internal PTC • Standard version: nominal voltage: 100 - 240V~ (- 15% + 10%) Frequency 50/60Hz • Low Voltage version: Nominal voltage: 24V~ (- 25% + 12%) Frequency 50/60Hz or 24V– (- 15% + 25%) • Power consumption 2.6W max included PTC L 1 Supply N 2 B 2.3.
2 - Electrical connections 2.3.2 PV CONTROL INPUT 2.3.3 AUXILIARY INPUT (option) D For current transformer CT Not isolated For the measure of the load current (see page 34) B For mA, mV mV mA 5 6 External Shunt 2.5Ω Rj >10MΩ D1 With 2 wires transducer 4…20mA PV 9 18V– [1] • Primary coil10A…100A • Secondary coil 50mA default 100mA jumper selectable B 5 watt burden resistor 0.5Ω for 1A secondary transformer coil 0.
2 - Electrical connections B 2.3.4 OP1 - OP2 - OP3 OUTPUTS The functionality associated to each of the OP1, OP2 and OP3 input is defined during the configuration of the instrument index l(see page 18). The suggested combinations are: Control A B C D E Single action Single action Double action Double action Double action OP1 Heat OP2-L Heat OP1 Heat OP1 Heat OP2-L Heat OP2 output can be Relay (Std) or SSR drive.
2 - Electrical connections 2.3.4-A SINGLE ACTION RELAY (TRIAC) CONTROL OUTPUT B 2.3.4-C DOUBLE ACTION RELAY (TRIAC)/RELAY (TRIAC) CONTROL OUTPUT Fuse OP1 OP1 4 Varistor for inductive load 24V only ~ 2.3.4-B SINGLE ACTION SSR DRIVE CONTROL B OUTPUT 10 Static relay OP3 14 Varistor for inductive load 24V only Coil of the heat load contactor Load 11 Relay output • SPST Relay N.O., 2A/250 V~ for resistive load, fuse 2A~ T Triac output • N.O.
2 - Electrical connections 2.3.5 ALARMS OUTPUTS B e The outputs OP1, OP2 and OP3, can be used as alarm outputs only if they are not used as control outputs. B 2.3.6 OP4 OUTPUT (option) PV or SP retransmission • Galvanic isolation 500V~/1 min • 0/4…20mA, (750Ω or 15V– max) 7 mA OP4 Load 8 Fuse 3 OP1 4 Coil of the load alarm contactor Fuse 15 B 2.3.
3 - Product coding 3 PRODUCT CODING The complete code is shown on the instrument label. The informations about product coding are accessible from the front panel by mean of a particular procedure described at section 4.2.2 page 21 3 1 2 3 3150 RUN 16 Hard B C D L M N Instrument Label P/N : M3-3150-0000 CONF : 2002 S/N : A0A-9809/0013 V~(L-N).
3 - Product coding 3.1 MODEL CODE The product code indicates the specific hardware configuration of the instrument, that can be modified by specialized engineers only. Line Model: M 3 Basic Accessories A B C D - E F G 0 / Configur.
3 - Product coding 3.2 CONFIGURATION CODING The configuration code consists of 4 digits that identify the operating characteristic of the controller, as chosen by the user. Section 4.6 at page 35 reports the instructions how to set a new configuration code.
3 - Product coding A If, when the controller is powered up for the first time, the display shows the following message 3 1 2 3 9999 Conf it means that the controller has not been configured yet. The controller remains in stand-by until the configuration code is set correctly (see chapter 4.6 page 35).
4 - Operations 4 OPERATIONS 4.1.A KEYS FUNCTIONS AND DISPLAY IN OPERATOR MODE When the measured When the measured PV control input value is greater than value is less than the sensor high range sensor low range in engineering units Operating Setpoint 3 Output status OP1 output ON LEDs OP2 output ON (red): OP3 output ON 274.8 1 2 3 RUN Start-up/Timer running (green) MAN 275.0 Tune running (green): blinking Menu access Setpoint setting Enter key for selection and value setting confirmation 4.1.
4 - Operations 4.2 DISPLAY During the operation, the parameters values cannot be modified by the user 4.2.1 OF THE PROCESS VARIABLES 274.8 275..0 274.8 °C 63.4 °C Out 47 t.Cur Note [1] See table page 37 [2] This display is not presented if the instrument has been configured as an On - Off controller [3] Value in Ampere. Only with CT option (see page 34) [4] Only with Timer option selected (see page 41) Operator mode 33 tM.r. 4.2.2 OF THE CONFIGURATION CODES 274.8 Operator mode 275..
4 - Operations 4.3 PARAMETER SETTING 4.3.1 NUMERIC ENTRY (i.e. the modification of the Setpoint value from 275.0 to 240.0 ) Operator mode Press $ or % momentariworking Setpoint ly to change the value of 1 unit displayed 274.8 275.0 every push Continued pressing of $ or % changes the value, at rate that doubles every second. Releasing the button the rate of change decreases. In any case the change of the value stops when it has reached the max/min limit set for the parameter.
4 - Operations 4.3.2 MNEMONIC CODES SETTING (e.g. configuration see page 35) Press the $ or % to display the next or previous mnemonic for the selected parameter. Continued pressing of $ or % will display further mnemonics at a rate of one mnemonic every 0.5 sec. The mnemonic displayed at the time the next parameter is selected, is the one stored in the parameter.
4 - Operations 4.3.3 KEYPAD LOCK 4.3.4 OUTPUTS LOCK To lock/unlock the keypad press the keys í and è simultaneously for 2 seconds. To confirm the keypad lock/unlock the display flashes once. The outputs are switched to the OFF status by pressing the keys í and %together. When the outputs are locked , the is displayed message #Off instead of the Setpoint value. To unlock the outputs press again the keys simultaneously (the Soft-start will be enabled). 3 274.8 3 operator mode 274.8 275.
4 - Operations 4.4 PARAMETERISATION 274.8 Parameter mnemonic Parameter value 275..0 Operator mode run/stop t.run Timer (if option installed) 35.0 p.b. Values modification Prameter Modification/ menu selection selection enter A Note [1] It is not presented if the controller has been configured with alarm n° 2 not active or of sensor break type. Digit N/M of the configuration code is assigned to 0 or 1. The parameter setting procedure has a timeout.
4 - Operations é PARAMETER MENU 33 pAss 5000 é 0 Password entry only if Code value ≥5000 (see pages 35…37) GROUP A2s.p 1st AL2 alarm threshold [1] GROUP tune 2nd Tune run/stop (PID algorithm only) (see page 28) Code entry from 5000 to 9999 Must be equal to the value of the parameter Code é 1 tiMe é YES é 0:5 d.bnd é 20 é t.c. C Op. H é Control output high limit (PID algorithm only) 10.0…100.0% é100:0 1:0 r.C.Ga Dead band (heat/cool configuration only) -10.0…10.
4 - Operations pass é s.p.s.U é énone 0 Start-up Setpoint (if option installed) s.p. l…s.p. H A3L.b é Off 1 hold time (if option installed) t.h.s.U Start-up t.LbA 0…500 min. Password entry only if Code value <5000 (see pages 35…37) AL3 latching and blocking functions none / Ltch bloc / Lt.bL high limit during Start-up Op.Hs Output (if option installed) 1 st.tM LBA delay (see page 31) 0ff= sensor break 1…9999 sec LBA é 0 sa.Op 0.0…100.0% time constant t.Fil Filter 0ff/ 1…30 sec (-100.
4 - Operations 4.5 PARAMETERS FIRST GROUP The controller parameters have been organised in group, according to their functionality area. # 2s.p A #A3s.p AL2 alarm threshold AL3 alarm threshold The alarm occurrences handle the OP1, OP2 and OP3 outputs, in different ways, according to the configured types of alarms, as illustrated.
4 - Operations Band alarm SP On Active Off out On Off hy full scale hy alarm threshold Active in full scale Proportional band This parameter specifies the proportional band coefficient that multiplies the error (SP - PV) #p.b. #t.i. Integral time It is the integral time value, that specifies the time required by the integral term to generate an output equivalent to the proportional term. When Off the integral term is not included in the control algorithm.
4 - Operations SECOND GROUP Setpoint ramp up Setpoint ramp down This parameter specifies the maximum rate of change of the Setpoint in digit/min. When the parameter is Off, this function is disabled. # l. u s #sl. d Setpoint low limit Setpoint high limit Low / high limit of the Setpoint value. # .p. l s #s.p. H AL2 alarm hysteresis AL3 alarm hysteresis Hysteresis of the threshold of both the alarms, that activate OP1 and OP2 control output. It is specified as a % of the full scale.
4 - Operations ALARMS WITH LBA (LOOP BREAK ALARM) AND SENSOR BREAK OPERATION Select the code 1 on n or o configuration indexes (see pages 18 or 19). The following parameter is then available: #T.LbA LBA delay Setting a value between 1 and 9999 sec the alarm works as LBA+Sensor break with delay [1] This condition is shown by means a red led as well as the blinking PV display. Setting OFF the alarm works as Sensor break with immediate action.
4 - Operations SECOND GROUP HEAT COOL CONTROL Soft-start control output value Value of the control output during the Soft-start activation time. #st.Op Soft-start activation time Time duration (starting from the power on) of the Soft-start function. #st.tM OP By a sole PID control algorithm, the controller handles two different outputs, one of these performs the Heat action, the other one the Cool action. It is possible to overlap the outputs. The dead band parameter d # b .
4 - Operations RETRANSMISSION A Heat /Cool actions separated Insert positive #d.bnd (0…10%) 100% value -100% #Op. H C Cool action adjusting Example with different relative cool gains =2.0 #r.C.Ga 0.1…10.0 100% =1.0 =0.5 -100% #Op.HC OP4 output, if present, retransmits linearised PV or the SP. On configuration (see page 37) it is possible to set: Output range 0=20 / 4=20 Retransmitted signal p.U. / r # etr #rt.H #d.b.nd #d.b.
4 - Operations CURRENT TRANSFORMER INPUT Example: • T/C S, range 0…1600°C • Output range, 4…20 mA • Retransmitted signal PV on 800…1200°C range mA 20 #retr = 4=20 #rt.H = p.U #rt.lo = 800 #rt.Hi =1200 With CT option it is possible to display the load current and set an alarm threshold.
4 - Operations 4.6 CONFIGURATION 274.8 The configuration of the controller is specified through a 4 digit code that defines the type of input, of control output and of the alarms. (sect. 3.2 page 18) Parameter value Operator mode 275..0 t.run Timer run/stop (if option installed) Parameter mnemonic 200.2 Conf Values modification Configuration Enter key for menu access selection and value setting confirmation Press $ or % to display the next parameter or the next code and change its value.
4 - Operations CONFIGURATION MENU A2s.p pAss 5000 1st GROUP 2nd GROUP Password entry only if Code value ≥5000 Code entry from 5000 to 9999 Must be equal to the value of the parameter Direct access to the configuration Code Entry of digits I-L-M-N of the configuration code (chapter 3.2 page 18 and 19) OK NO tune YES I L M N sc.Hi High range [2] (linear scale only) -999…9999 units[1] (see table) Unit Engineering t.
4 - Operations pass Password entry only if Code value <5000 Note [1] Table of the supported Engineering Units. Centigrade degrees* Fahrenheit degrees * 33 none Code entry from 0 to 4999 (33 default from factory) The entered password must correspond to the one store in the Code parameter. Volt mA Ampere OK YES mV NO Bar PSI A Direct access to the configuration A From parameterisation (see page 27).
5 - Automatic tune 5 AUTOMATIC TUNE Start/stop of the Fuzzy Tuning The Tuning operation can be started or stopped any time. 274.8 275..0 Operator mode press until stop tune strt tune 38 To start select strt To stop select stop The green led { blinking goes on when the Fuzzy Tuning is in progress. At the end of this operation, the calculated PID terms parameter are stored and used by the control algorithm and the controller goes back to the operator mode. The green led { becomes off.
6 - Special functions 6 SPECIAL FUNCTIONS Two special functions are available: 6.1 Start-up 6.2 Timer In order to have the above functions the product code digit E must be 2 (see page 17) For example: M3 3100-2000 To select these functions use the parameter: Timer/Start-up operator mode (see page 35). #t.Mod A Selecting Timer or Start-up, the Soft-start function is disabled, therefore the parameters #st.Op and #st.tM will not be shown. (see page 27) 6.
6 - Special functions continued 6.1 START-UP FUNCTION There are two possibilities: A Start-up Setpoint # s p. s U lower than the local Setpoint. The “Hold” phase starts when the process variable PV achieves the #sp.sU (with a tolerance of 1 digit). B Start-up Setpoint #sp.sU greater than or equal to the local Setpoint. When the process variable PV achieves the local Setpoint (with a tolerance of 1 digit), the Start-up function passes directly to the “Off” phase.
6 - Special functions 6.2 TIMER FUNCTION To use AL3 in addition to this function, set the parameter #Con2 (AL3 configuration code) to # 0.. A The Timer can’t be enabled with Heat/Cool control. The two following parameters (see page 37) must be set to select one of the six possible types of Timer. Timer/Start-up operating mode By this parameter can be defined: - the counting start time - the control output status at the end of the counting #t.
6 - Special functions When the timer is running it is always possible to see the remaining time and to modify it. 850 RUN 850 Operator mode and Timer running Press until 234 RUN If there is a power failure during the Timer execution, the value of the elapsed time is lost. 350 Operator mode 350 Press until Remaining time value stop t.run To start select strt tM.r. Value change 60 42 Depending on the Timer action #t.
6 - Special functions 6.2.4 TIMER COUNTING MODES A Counting start time inside C Counting start time = timer the band, end in control mode. launch time, end in control mode. E No control action during the counting time. The time counting starts only when the error is inside a ± 1 digit band. The control action is not affected by the Timer function. The time counting starts when the timer is launched and the control output is forced to zero.At the end, the control action starts. Timer launch #tiMe #t.
7 - Technical specification 7 TECHNICAL SPECIFICATIONS Features (at 25°C environmental temp.) Description Total configurability (see par. 3.2 page 18 par. 4.6 page 35 From keypad or serial communication the user selects: - the type of input - the associated functions and the corresponding outputs - the type of control algorithm - the type of output and the safe conditions - the type and functionality of the alarms - the values of all the control parameters.
7 - Technical specification Features (at 25°C environmental temp.
7 - Technical specification Features (at 25°C environmental temp.) Description Hysteresis 0.1…10.0% c.s. Active high AL2 - AL3 alarms Setpoint OP4 PV or SP retransmission (option) One shot Fuzzy-Tuning with automatic selection Serial comm.
7- Technical specification Features (at 25°C environmental temp.) Description General characteristics Compliance to the CE standards Electromagnetic (see page 2) compatibility Protection EN60529 (IEC 529) IP65 front panel UL and cUL Omologation File 176452 1/ DIN - 48 x 48, depth 120 mm, weight 130 gr. apx.
1 WARRANTY We warrant that the products will be free from defects in material and workmanship for 3 years from the date of delivery. The warranty above shall not apply for any failure caused by the use of the product not in line with the instructions reported on this manual. 48 G.&P. Grafica & Pubblicità • Gazzaniga (BG) • e-mail: G & P @ m a i l . csg-net .