Instruction Manual

I
NSTALLATION REQUIREMENTS
To minimize the risk of injury, the switch enclosure must be
selected according to the area classification and installed
according to the required safety and electrical codes.
Before operating the switch all conduit entries and/or junction
boxes need to be closed according to the required safety and
electrical codes.
To attain the degree of protection listed on the switch it may
be necessary to add required conduit fittings.
The switch must be protected from moisture, shock and/or
extreme vibration.
The ambient temperature limits for switches are –20 to 150°F,
(–28 to 65°C).
CAUTIONS
Always install the cover after wiring the switch and before
power is supplied.
Before removing the cover in hazardous areas be sure there
is no e
xplosive atmosphere present and the power supply is
turned off.
For ATEX approved switches all safety locking devices and
electrical earthing must be installed or connected before
operating.
Never carry a temperature switch by holding only the stem,
bulb or capillary.
Do not exceed ranges, current and/or voltage limits.
The protection degree of the switch is only valid when the
switch is installed in accordance with all safety and electrical
codes and regulations.
CLEANING
Never use aggressive solvents.
Do not use high pressure water to clean the switch.
MAINTENANCE/TROUBLESHOOTING
All Ashcroft switches require little or no maintenance.
Be sure that the case is closed at all times.
When the switch is exposed to process media that may hard-
en and/or build up in the pressure port, the switch should be
removed and cleaned as needed.
If the switch does not function, only trained and skilled per-
sonnel should check on the wiring, power supply and/or
mounting.
If the prob
lem can not be solv
ed, please contact one of the
Ashcroft affiliates or distributors.
ELECTRICAL CONNECTIONS
Only trained and skilled personnel are allowed to install the
wires to the electrical terminals of the switch.
Cable couplers, glands and conduit connectors must have the
correct electrical approvals.
Alw
a
ys f
ollo
w safety and electrical regulations when connect-
ing these de
vices
.
The system ground of the device is marked with a green
colored scre
w and/or b
y the ground symbol.
ATEX approved switches have an external ground screw that
must be connected.
Micro switch terminals and wire color codes:
NO (Normally Open) Blue
NC (Normally Closed) Red
C (Common)
White
Gr
ound
Green
(F-Series only)
MICRO SWITCH CODE ELECTRICAL RATING
Single Dual Single Dual Vac Vdc
K KK 20 61 15A, 250V 0.4A, 120V
W WW 21 65 5A, 250V 6A, 30V
P PP 22 67 5A, 250V 2.5A, 28V
C N/A 23 N/A 22A, 250V
G
GG 24 64 15A, 480V 0.25A, 250V
S N/A 25 N/A 10A, 125V 10A, 125V
F FF 26 62 15A, 250V 0.4V, 120V
Y YY 27 63 15A, 250V
U UU 28 N/A 15A, 250V 6A, 30V
E EE 29 N/A 15A, 250V 6A, 30V
M MM 31 70 1A, 125V 50mA, 60V
J JJ
32
68
11A, 250V
5A, 30V
L LL 42 71
1A, 125V
N/A N/A 50 N/A 15A, 250V
H HH 35 N/A 10A, 250V 0.25A, 250V
©
2007 Ashcroft Inc., 250 East Main Street, Str
atf
ord, CT 06614-5145, USA,
T
el:
203-378-8281, F
ax:
203-385-0499, www
.ashcroft.com
All sales subject to standard ter
ms and conditions of sale
.
I&M009-10030-10/00 (250-3136) AMR 5/07
Installation and Maintenance
Instructions for CE Mark on ASHCROFT
®
Switches/Low Voltage Directive 73/23/EEC
TABLE 1: MICRO SWITCH ELECTRICAL RATINGS