Installation Guide
13
INSTALLATION MODEL IN SOLID FUEL BURNING FIREPLACES
This model may be installed in a masonry fi replace. The fi gure below demonstrates the required dimensions.
NOTE: See “Producing Adequate Air for Combustion And Ventilation”
NOTE: Installer of this appliance must mechanically (peel and stick) attach marking supplied with this unvented
appliance before installing to inside of fi rebox of solid-fuel burning fi replace or listed ventless fi rebox enclosure
into which unvented fi replace insert is installed. See example of marking on the “Gas Pressure Check” section
of this manual.
CAUTION: Cutting any sheet-metal parts of solid-fuel burning fi replace or listed ventless enclosure in which
unvented fi replace is to be installed is prohibited.
NOTE: “If factory-built fi replace has no gas access hole(s) provided, an access hole of 1.5 inch (37.5) diameter
or less may be drilled through lower sides or bottom of fi rebox in a proper workmanlike manner. This access
hole must be plugged with non-combustible insulation after the gas supply line has been installed.”
“Refractory, glass doors, screen rails, screen mesh and solid-fuel log grates (if applicable) can be removed
from fi replace before installing unvented fi replace insert.”
NOTE: After the unit is positioned in fi replace, mark trim panels as follows:
A. Set side panels in place, fl at against fi replace. Mark down inside edge of trim panel to make a vertical
reference line.
20"
24"
7"
7"
RIGHT
SIDE
LEFT
SIDE
25 1/8”
35-9/16”
13-3/4”
FRONT
CEILING
SECTION III