Installation Guide

29
SECTION IX
AIR FOR COMBUSTION AND VENTILATION INSIDE BUILDING
This fresh air would come from an adjoining uncon ned space. When venting to an adjoining space, you must
provide two permanent openings: one within 12" of ceiling and one within 12" of oor, on wall connecting two
spaces. (See Options 1 and 2 below.) You can also remove door into adjoining room. (See Option 3 below.)
WARNING: REWORK WORKSHEET, ADDING SPACE OF ADJOINING UNCONFINED SPACE.
COMBINED SPACES MUST HAVE ADEQUATE AMOUNT OF AIR TO SUPPLY
ALL APPLIANCES IN BOTH SPACES
NOTE: Each opening shall have a minimum free area of 1 square inch per 1000 BTU’s per hour of the total
input ratings of all gas utilization equipment in the con ned space, but not less than 100 square inches.
Ventilation Air From Inside Building
WARNING: THIS HEATER MUST HAVE ADEQUATE AMOUNT OF AIR FOR PROPER OPERATION.
IF NOT, POOR FUEL COMBUSTION COULD RESULT. READ THE FOLLOWING INSTRUCTIONS TO
ENSURE PROPER AMOUNT OF AIR FOR THIS AND OTHER FUEL-BURNING APPLIANCES IN YOUR
HOME.