SECTION VI
VENTED
(1) This appliance must be installed only in a solid-fuel burning fireplace with a working flue
and constructed of non-combustible materials.
(2) A minimum of 34 sq. in. (Min. 6" chimney) or see page 41, permanent flue opening must
be provided by either the fireplace chimney or chimney damper to vent the flue gases.
(3) Solid fuels shall not be burned in a fireplace where a decorative appliance is installed.
(4) Any chimney damper must be fixed in a manner which will maintain the minimum
permanent vent opening at all times.See figure 11.
NOTE: See chart on page 41.
F
i
g
u
r
e
1
1
MINIMUM FIREPLACE DIMENSIONS FOR LOG SETS MANUFACTURED BY NEW
BUCK CORPORATION FOR SOLID FUEL BURNING FIREPLACE OR MASONRY
FIREPLACE AND PREFAB OR MANUFACTURED FIREPLACES.
NOTE: When using logsets with the Model 19HS heat shield see page 30 for clearances.
MODEL HEIGHT OF WIDTH OF WIDTH AT DEPTH OF
OPENING OPENING REAR FIREPLACE
AT FRONT
18 17" 25" 18" 14"
24 17" 30" 24" 14"
30 17" 36" 26" 14"
WARNING: A fireplace screen must be in place when the appliance is operating and,
unless other provisions for combustion air are provided, the screen shall have an opening
(s) for introduction of Air For Combustion And Ventilation.