User's Manual

Table Of Contents
50
ASSA ABLOY Hospitality
66 8003 015-3
Appendix A: Quick reference of technical data
Thermostat deadband
Configurable 1-3 °F; default is 2 °F
Heat/cool switching deadband
Configurable 2-4 °F; default is 3 °F
Freeze guard
39 °F / 4 °C
Refresh cycle
Optional
Humidity
Optional
Intelligent switch
Configurable: Disabled/use RV output/use G2 output;
default is disabled
Room not occupied timer
Configurable 1-120 minutes; default is 8 minutes
Room not sold timer
Configurable 12-24 hours; default is 16 hours
Compressor delay
(dwell-off time)
Default is that the dwell-off time is off; it is only applicable
when 'heat pump' is chosen as HVAC type.
In the 'heat pump' case, the thermostat will automatically
force the dwell-off time to be on - it is then 5 minutes and
cannot be changed. The dwell-off time prevents short-cycling
of the compressor.
Required Visionline version
1.15.0 or higher for full functionality of
thermostat profiles
Required Orion Service version
1.3.0 or higher
Table A1