ASSA ABLOY Hospitality
66 3081 004-23
7. Commissioning
7.1 Printing a status report
SysMon provides a simple method for printing out the status of all the connected
devices in the online network.
1. In the Online Network view in SysMon, click the Print Status button.
Note: When clicking Print Status, it is possible to choose where to save
the status report.
Figure 50
2. A Microsoft Excel spreadsheet will be written to the TempData folder in your
installation folder.
The spreadsheet provides detailed information for each connected RT and EN; see
example screenshot on next page. The information written to the document includes:
name of the PAN (GW) the device is connected to
RT name
room; if it is an EN
IEEE address
version for RT, EN or GW; in the last case, GW firmware as well as version in
the PAN coordinator (PC) are stated
network address
average link quality between the device and its parent
time that last LQI measurement was taken
last link quality index (LQI) recorded
time for last successful command since the server was restarted; if this column
says 'n/a', there has not yet been any answer from the lock