User's Manual

Table Of Contents
21
DRAFT 66 8003 001-8
1.7.2 Advanced parameters
Parameter
Description
Available choices
Default setting
Room not occupied timer
(Thermostat profile details
dialog, Timeout alternative)
This is the amount of time
the thermostat maintains
the guest setting after
the room has entered
the unoccupied state.
1-30 minutes
8 minutes
Room not sold timer
(Thermostat profile details
dialog, Timeout alternative)
When the room has
been unoccupied for this
number of hours, it will
enter unsold mode.
12-24 hours
16 hours
Thermostat deadband
(Thermostat profile details
dialog, Deadband alternative)
The range the temperature
is allowed to drift from the
setpoint before the heat or
air conditioner is turned on
1-3 ºF
2 ºF
Heat/cool switch deadband
(Thermostat profile details
dialog, Deadband alternative)
This parameter is only
applicable if auto switching
mode has been chosen
under the HVAC tab in
the Thermostat profile
details dialog.
The heat/cool switch
deadband is the range the
temperature is allowed to
drift before switching from
heat to cool or cool to heat.
2-4 ºF
3 ºF
Max HVAC runtime
(Tools/Options dialog,
expand Energy management
and choose General)
An alarm is triggered if
a HVAC runs this long
without turning off.
30-300 minutes
120 minutes
Max setback override
(Tools/Options dialog,
expand Energy management
and choose General)
The Orion EMS features
may be overridden when
needed, e.g. for VIP guests
where no setbacks should
apply; click here for details.
If a number of hours is
entered at 'Max setback
override', an alarm will
be triggered if the setback
override exceeds this
number of hours. If the
default 0 hours is used,
no alarm will be triggered.
0-99 hours
0 hours
Maintenance intervals
(Tools/Options dialog,
expand Energy management
and choose Maintenance)
Number of hours
before the three
different maintenance
alarms should be
triggered;
the valid range is
0-65 535 hours.
- Maintenance counter 1
is for fan time/total