User's Manual

Table Of Contents
32
DRAFT 66 8003 001-8
Note: By clicking on any of the pie charts Occupancy Status or HVAC Run Status,
the corresponding Real time room status dialog will be shown. By clicking on any of
the bars in the Maintenance or Current Alarms bar chart, more information about the
alarms will be shown.
The Occupancy Status diagram shows how large share of the total number of
guest rooms that are
occupied
unoccupied
unsold
See section 1.1 Basic EMS logic for more information about the different states above.
The HVAC Run Status diagram shows how large share of the HVAC systems that are
cooling
heating
off
The Runtime % diagram shows
actual energy consumption in runtime
energy consumption if no EMS had been used
savings in energy consumption when EMS is used; Actual curve minus
no EMS curve
occupancy
The Maintenance diagram shows the number of
preventative maintenance schedules; maintenance intervals 1-3
battery alarms from motion sensor
offline rooms (motion sensor/lock offline; thermostat offline)
The Current Alarms diagram shows the number of alarms related to
security; door left open
HVAC
- thermostat cooling on highest fan speed – temperature rising
- thermostat heating on highest fan speed – temperature dropping
- HVAC running longer than maximum runtime (default 120 minutes)
without reaching setpoint
- too long duration of setback override
device; no motion detected for 24 hours in spite of door activity
freeze; the temperature in a room goes below 39 ºF = 4 ºC
excessive occupancy; if a room has had occupancy without door movement
for 48 hours
Note: When any of the alarms for maintenance 1-3 has been taken care of,
the concerned maintenance counter must be reset from Orion Service; see section
about configuring thermostat in Quick reference guide Orion Service.