If '2-pipe fan coil with automatic switching' is chosen at Type, the alternatives
Pipe sensor and Trigger level will be shown.
1. If the pipe sensor is a bimetal switch (open or
closed depending on the temperature it senses),
choose at Pipe sensor the applic able one of
'Cooling' and 'Heat ing'.
2. Ifthepipesensorisan1k NTC resistor,
a
Trigger level (in the range 0-100%) for
switc hing between heat and c ool should be
entered. When the t emperat ure reac hes the
switch-over-temperature (default 3 ยบF; this is
chosen under the Deadband alternative in the
Thermostat profile details dialog, see Figure
57), it is c hecked whether the pipe sensor has
reached the trigger level so that the thermostat
can change mode from heating to cooling or
vice versa.
Note:
When '2-pipe fan coil with automatic
switc hing' is c hosen as HVAC type, t he c ooling
relay (Y
) is the only relay that applies, forc ed by
the thermostat.