Installing the Control Unit
Page 2-7
AC Power and Grounding
Auxiliary equipment requires additional AC outlets.
If a printer or PC is installed on the system, it must be plugged into the
same AC branch as the power supply of the basic carrier.
If the printer or PC is 50 ft. (15 m) or more from the control unit, or is
plugged into a different AC circuit, Asynchronous Data Units (ADUs)
must be installed as well. Chapter 5, ‘‘
Installing the PC, CAT, or Printer’’,
includes complete installation instructions.
The AC power requirements indicated in “AC Outlet Tests,” on page 2-8,
must be met.
Figure 2-1. AC Grounding Requirements
Ground Bar Mounted
on a 4" Box (Square
"D" PK9GTA or
approved equivalent)
From AC
Load Center
(2 separately
fused 15 A
circuits)
Ground Wire
#14 AWG
4" Box (RACO 230
or equivalent)
HUBBELL
Receptacles
(5262 15 A
or equivalent)
4" Cover 
(RACO 807
or equivalent)
Approved
Building Ground
#12 or #14 AWG Copper
Wire to Each Power Supply
Grounding Screw
Single-Point
Ground
Ground Wire
#6 AWG Copper