Specifications
Environmental Specifications
Control Unit
Fully loaded basic carrier
451b (20.4 kg) 14” W x 23” H x 12” D
(35.6cm x 58.4 cm x 30.5 cm)
Fully loaded 2-carrier
90 lb (40.8 kg) 25” W x 23” H x 12 D
(63.5cm x 58.4 cm x 30.5 cm)
Fully loaded 3-carrier
1351 b(61.2 kg) 37” W x 23” H x 12” D
(94 cm x 58.4 cm x 30.5 cm)
Mean Time Between Failures
2.1 years
(mean or average time the system is expected to
operate before any type of failure occurs)
Mean Time Between Outages
4.0 years
(mean or average time the system is expected to
operate before a failure affecting more than 25% of
extensions or lines for more than 15 seconds occurs)
Backboard
■ Without SYSTIMAX® 6’ W x 3’ H x 3/4” D (182,9 cm x 91.4 cm x 1.9 cm)
■ With SYSTIMAX
7’ W x 4’ H x 3/4’’ D(2l3.4cmx 121.9cmx 1.9 cm)
Backboard Mounting Hardware Requirements
Wood surface
Wood screws
Concrete surface, brick, cmdcr block
Masonry anchors
Plaster, plasterboard
Toggle bolts
Sheet-metal surface
Sheel-metal screws
■ Hardware should have a combined pullout force of 650 lb (294.8 kg),
■ When mounting to sheet-metal walls, attach to structural members.
Location
■ Within 5’ (1.5 m) of dedicated AC power outlet (1 plug per carrier)
■ Within 1000 cable feet (304.8 m) of telephones
Heat Dissipation
Fully loaded basic carrier
500 Btu/hr (35 callsec)
Fully loaded 2-carrier
1000 Blu/hr
(70 cal/sec)
Fully loaded 3-carrier
1500 Btu/hr
(105 cal/sec)
Power Requirements
Basic carrier
117VAC
60 Hz ± 5% 3A
2-carrier
117VAC 60 Hz ± 5% 6A
3-carrier
117VAC
60 Hz ± 5% 9A