U s e r M a n u a l e m a n u a l d ’ i n s t a l l a z i o n e e d ’ u s o ATAG WiZe programmable modulating room thermostat GB / I / TR 8X.52.03.01/03.
Contents 1 1 Page Key functions .....................................................................4 Specifications ....................................................................6 2 Mounting and initial operation ...........................................9 2.1 Mounting ..................................................................9 2.2 Initial operation ....................................................... 11 3 Manual mode .................................................................
Key functions 1 2 3 4 5 6 7 8 9 Time bar (24 hours) of the clock program (from 03.00 to 03.00 hours). The bar displays the day program set. Tap symbol for tap water Comfort/Economy setting. • Symbol visible: Comfort setting always on or switching on/ off automatically. • Symbol not visible: Economy setting. Radiator symbol for central heating operation. • Symbol visible = central heating operation possible. • Symbol not visible = central heating operation not possible.
10 Current room temperature (measured). A flashing °C symbol indicates that switch-on optimization is active. . Pressing this key displays the user menu 11 Menu key (chapter 5.1 refers). The standard display will reappear when pressing this key again or when no key is being pressed for 2 minutes. 12 The arrow symbols become visible when the corresponding key has a function. 13 Function keys. The numbers are not printed on the keys but only mentioned in this instruction manual.
1. Specifications This chapter explains how the clock thermostat and some of its functions work. • • • • • • • • • • No batteries. Loss of voltage Manual mode Central heating’s clock program. Self-learning switch-on optimization: Comfortably warm on time. Additional savings in Economy setting. On-screen device information. Modulating central heating control. Weather dependent control. Timer function. No batteries For its functioning the clock thermostat receives its energy from the connected boiler.
Self-learning: Comfortably warm on time (only in automatic mode) The self-learning switch-on optimization ensures that the required temperature is reached at the time programmed. Since outside temperatures vary daily, the thermostat re-determines every day at what time the boiler has to start up in the morning to ensure it being warm on time. If that temperature has not been reached at the time set, it will start heating up earlier the next morning. The same applies the other way round.
Modulating central heating control The WiZe clock thermostat measures the room temperature and uses it to determine the area’s heat demand. Depending on room temperature the thermostat determines the water temperature required by the boiler. As a result the boiler also determines the capacity required resulting in optimum heat input to the house combined with the lowest energy consumption possible. Weather dependent control The WiZe clock thermostat can also be used as a weather dependent control.
2. Mounting and initial operation 2.1 Mounting 2.2 Initial operation 9 11 2.1 Mounting A .Choose a suitable location for mounting the thermostat. Suitable mounting location: At a height of approx. 1.5 m, away from windows and doors; on an internal wall without obstacles around the room thermostat. Wrong mounting places: • In a place where the sun can shine directly on the thermostat. • On a cold outside wall (maybe fitting insulation material behind the thermostat).
B. Remove the rear panel C. Mount the rear panel on the wall (A refers) Use the rear panel as a template to mark the holes! Seal the hole where the wiring originates to prevent likely draught. Use the screws and plugs supplied. D. Fit wiring to rear panel Make sure that the boiler plug has been removed from its socket! Only connect the wiring to the Z-ready/bus thermostat connection of the boiler.
2.2 Initial operation Plug the boiler’s plug into the socket. When voltage has been supplied to the thermostat for the first time, you will see this screen. Select language (English is default) Italian and Turkish are also possible, select using arrow keys. Press (OK). You have now set the language.
3. Manual mode 3.1 Activating manual mode 3.2 Manual thermostat mode 12 13 3.1 Activating manual mode You can also use this thermostat without the clock program being switched on. No clock bar = manual mode If you do not see a clock bar on the screen, then proceed to chapter 3.2. Clock bar visible = clock program active (automatic). When you do see the clock bar on the screen, then please activate manual mode.
3.2 Manual mode thermostat (clock program not activated) Once the thermostat has been set to manual mode (3.1 refers) you can change the required temperature as follows: The standard screen will display the current room temperature. Press an arrow key once and the set required temperature will start flashing. actual room temperature Increase or decrease the set temperature using the arrow keys and the new required value you see displayed will be set instantly. The temperature can be adjusted by 0.
4. Clock program central heating 4.1 Activating central heating’s clock program 4.2 Set the three required room temperatures 4.3 Select a pre-programmed weekly program 4.4 Amend the weekly program 4.5 Adjusting temperature temporarily 14 15 17 18 23 4.1 Activating clock program for CH Check whether the clock program has been activated: You can activate the clock program as follows: Clock bar visible = clock program active (automatic). If you do see a clock bar on the screen, then proceed to chapter 4.2.
4.2 Set the three desired room temperatures (low – medium – high) Three temperatures can be selected for the clock program controlling automatic temperatures, every half hour of the day you can select one of these three temperatures. In the example below the indicated temperatures represent factory settings.
Set the required (middle) temperature T2 using the arrow keys. When you press you will return to the previous screen (T1); (factory setting = 20,0°C) Made a mistake? Press the menu key for the starting screen. The set temperature flashes and is set immediately. Press (»); Set the required (highest) temperature T3 using the arrow keys. Press the menu key to return to the standard screen. (factory setting = 21,0°C) Continue with chapter 4.
4.3 Select a pre-programmed weekly program To make settings easier 5 week programs have been preprogrammed. Se below (1 to 5 incl.). Here you can select a program best suited to the week program required in the end. Chapter 4.4. tells you how the selected program can be further adjusted. The small blocks indicate the set temperatures: • One small line = T1 (low) • One small line and 1 small block above = T2 (middle) • One small line and 2 small blocks above = T3 (high) The time bar runs from 03.
Made a mistake? Press the menu key for the starting screen. Using the arrow key to select one program (no’s 1 to 5). Following selection press: (OK): Program has been adjusted or (CANCEL): Program not adjusted. After this the program menu is displayed again. Continue with chapter 4.4 4.4 Adjusting the weekly program Below please find an example of further adjustment of a preprogrammed day (this example refers to week program 1). The clock bar for Monday displays the standard adjacent picture.
This clock bar displays the following: - 03:00 - 07:00 hour: T1 (e.g. 17°C) - 07:00 - 16:00 hour: T2 (e.g. 20°C) - 16:00 - 23:00 hour: T3 (e.g. 21°C) - 23:00 - 03:00 hour: T1 (e.g. 17°C) You can adjust the day setting as follows: When you are in the program menu (as shown at *), continue at *). If you are not in the program menu; Press the menu key Press ; (»); Press (PRG); You are now in the program menu. Made a mistake? Press the menu key for the starting screen. *) MO = Monday.
Press (NONE). Now, using the arrow keys, you can run through the time bar without the temperature changing. Use the arrow key to proceed to 7.00 hours; Press (SET); Press (T2); Use the key to run through the time bar until 16:00 hours appears on the screen. The small blocks which are no longer flashing have been set, i.e. for 7:00 to 16:00 hours inclusive T2 has been set. Made a mistake? Did you go too far when changing the temperature? You can correct this as follows.
Run through the time bar using the arrow keys up until 23:00 hours inclusive; Press (SET); Press (T3); Run through the time bar using the key up until 00:00 hours inclusive; The small blocks that are no longer flashing have been set. Consequently, for 16:00 to 00:00 hours inclusive (=24:00) T3 has now been set. Straightaway the change has now been implemented. Copy day program to the following day When the screen shows MO you can use the arrow keys in the time bar to proceed to the next or previous day.
Summary setting of week program The screen displayed in the PROGRAM MENU. Consecutively press , (»), (PRG) and you will see the program menu; Press (SET) and here select ‘NONE’ if you wish to go to a certain time without changing anything. Run through the time bar with the arrow keys and . The clock’s time is running along just like the small flashing blocks in the time bar. Select T1 = , T2 = or T3 = at “SET” when you are on the “TIME” at which you wish to change the temperature.
4.5 Temporary adjustment of the temp. (with activated clock program) You can temporarily adjust the temperature as follows: On the screen you see the current room temperature. Press once on an arrow key or . You now see the programmed temperature (required). Using the arrow keys and you increase or decrease the programmed temperature (by 0.5°C). After 6 seconds the screen returns to its original situation (or after pressing the menu key ( ).
5. User settings This chapter explains how you can adjust certain settings. It gives recommendations with which you yourself can determine the best setting for your installation. At the same time it explains how you can read information from the boiler, such as boiler pressure. 5.1 Summary of user menu 5.2 Comfort / Economy setting 5.3 Using central heating timer 5.4 Reading device information 5.5 Adjusting hot water and central heating set point 5.6 Summary of settings menu 5.
5.2 Setting Comfort - / Economy setting (hot water) (with exception of Q-Series) When the boiler has that facility, the thermostat can be used to set the boiler’s hot water function to Comfort or Economy. Check the boiler’s manual for any settings required for this purpose. What does the Comfort/Economy setting imply? Most combination boilers have a function to supply hot water quickly, the so-called Comfort setting (with exception of the Q-series).
2 Continuous Economy: (Tap symbol not visible). (= Comfort off) (=Comfort OFF) Press ; Press (DHW); Press (OFF); 3 Automatic switching between Comfort/Economy settings in accordance with central heating’s clock program During the day the Comfort setting is on (during T2 and T3) and at night the Economy setting (during T1). Of course this only works when the central heating’s clock program has been activated: the time bar has to be visible at the top of the screen. 4.1 refers.
Press (AUT); You are now returning to the standard screen. 4 Automatic switching between Comfort/Economy settings in accordance with own hot water clock program Using this option you can determine when you want the boiler set to Comfort and when to Economy, automatically 7 days a week. This separate hot water program differs from the central heating’s clock program and can also be used when you have switched the thermostat to manual mode. During ( ) the boiler is set to Economy and during ( ) to Comfort.
* Press ; Press ; Press (PRG). If you do not see this screen, refer to previous section. Press (DHW); Press (PRE); Use arrow keys to select program 1 or 2. Refer to following information. Then press . You may select 2 preprogrammed day programs. T1 = = Economy setting T2 = = Comfort setting. For every day of the week you can now program at what time the boiler has to be in the Comfort setting and when in the Economy setting. Start again with * on this page.
5.3 Use the central heating’s timer (party program) Only when the central heating’s clock program is active you can temporarily set a different temperature using the central heating’s timer. With a minimum of 30 minutes and maximum of 12 hours. Press ; Press (CH); Press (TMR); Press (TIME); Using the arrow keys set the required duration of the period during which you wish to retain the temperature (e.g. 3 hours). Press (SETP); Set the required temperature using the arrow keys.
If you wish to end the set time earlier, just select the previous setting. Press ; Press (CH); a If you do use the clock program: Press (AUT) (clock bar is again visible on the screen). bIf you do not use the clock program: Press (ON); Using the central heating’s timer when the thermostat is set to “manual mode” implies that at the end of the TIMER function the temperature will not return to the temperature set initially.
1. Outside temperature. If _ _ _°C appears on the screen, then there is no outside sensor connected or it is not working. previous next 2. Pressure of central heating installation. The correct pressure has to be between 1.4 and 1.7 bar. Also have a look at the boiler to read the water pressure allowing you a proper check and top up if required. You may also refer to the boiler’s manual. 3. Central heating’s input temperature inside the boiler 4.
5.5 Adjusting DHW and CH set point All ATAG boilers allow for adjustment of the hot water temperature setting (= tapwater setpoint) and maximum central heating temperature (= central heating setpoint). When the WiZe thermostat is connected to the boiler, these adjustments may be set on both the boiler and thermostat. The last setting is always the current setting, regardless of where (boiler or thermostat) the setting has been activated. Please refer also to the boiler’s manual.
You can adjust the tapwater setpoint as follows: Press ; Press (»); Press (SET); Press a number of times on (») until you see DHW SETP. DHW SETP = DHW-setpoint (= control value for hot water temperature). Recommendation: Do not change the setpoint if it is not urgently required. ATTENTION! This setting is not the same as the hot water temperature coming out of the tap. Press the arrow keys to adjust the value. The value is set immediately.
5.6 Overview of settings menu Settings for the room thermostat and boiler. Press ; Press (»); Press (SET); Using the arrow keys ( and ) you can change the settings. ATTENTION! When the on-screen value changes, then it has been adjusted instantly. Standard Range ROOM T1 1st temperature for the clock pro15,0 7-35* gram, refer to chapter 4.2 ROOM T2 2nd temperature for the clock 20,0 7-35* program, refer to chapter 4.2 ROOM T3 3rd temperature for the clock pro21,0 7-35* gram, refer to chapter 4.
5.7 Resetting the exact day and time (e.g. summer/winter time) You can set the right time as follows: Press ; Press (»); Press (CLOCK); Press (DAY) and the day indicator starts flashing. Set the correct day using the arrow keys and . Press (HOUR) and the hour indicator starts flashing. Set the correct hour using the arrow keys and . Press (MIN) and the minute’s indicator starts flashing.
5.8 User recommendations / holidays Keep radiators placed in the area with the room thermostat always open. The actual temperature and room temperature measured by the thermostat may differ slightly depending on the installation and position of the room thermostat . This may be the case, for instance, when the thermostat is mounted on an outside wall. Consult your installer for further information.
Prevent freezing of your central heating installation When the thermostat has been switched off for both the Comfort setting and the central heating (the (!) symbol is visible), the thermostat will keep room temperature at a minimum of 5°C (Frost prevention). This is the case when ‘UIT’ (OFF) has been selected in the central heating menu and the tapwater menu. However, it is advisable not to set the thermostat lower than approx. 12°C.
The boiler comes on earlier than the time set on the central heating’s clock program. • The thermostat will want to reach the required temperature at the time set. As a result the boiler will start heating up earlier, this is the so-called self-learning switch-on optimization (chapter 1 refers). The boiler’s starting time may be different every day, because the moment the thermostat has to come on to reach the required temperature on time is being recalculated every day. This is a normal situation.
Display faults on the thermostat’s screen The thermostat can also relay boiler faults. Therefore, first check whether the fault is not caused by the connected boiler. Refer to the boiler’s manual for additional explanation regarding the boiler fault. If it reads “Err” instead of the temperature then there is something wrong with the boiler’s thermostat.
Press (»); You can see the boiler’s error-history. When you press (») you will see a list of errors that occurred in the past. Press the menu key ( ) and you will return to the standard screen. Refer to the boiler’s manual to see a description of the codes. The central heating’s pressure is too low. Top up the central heating system. Refer to the boiler’s manual for additional explanations in this respect. This fault implies that the thermostat is not working. Consult your installer.
Dismantling and loss of voltage Loss of voltage The thermostat works without batteries and obtains its required energy via the boiler. When the thermostat is removed from its mounting plate, all settings are stored in the memory. Only after an interruption of approximately 4 hours do you have to reset the day and time. Dismantling Disconnect the boiler from the mains (pull the plug from its socket or use the on/off button). • The thermostat hinges at the top and is clamped at the bottom (in the middle).
7 Technical specifications Technical specifications dimensions (hxwxd): weight: electrical supply: connected boiler) communication protocol: electrical connection: IP-class: storage conditions: (no condensation) clock function tolerance: room temperature tolerance: 77,5 x 155 x 28 mm approx. 136 grams nominal approx. 5V (from Z-bus (OpenTherm) 2-wire, polarity insensitive IP30 0-40°C / 10-90% humidity ±10 minutes /year ± 0.5°C This revised publication supersedes all previous installation instructions.
87
We reserve the right to make changes • Wijzigingen voorbehouden Sous réserve de modifications • Änderungen und Irrtümer vorbehalten Ci si riserva il diritto di apportare eventuali modifiche www.atagheating.