User Manual

4
SMRT36
Megger Relay Test System
Current Amplifier - Extended Power Range
The SMRT current amplifier provides a unique flat power curve from
4 to 30 Amperes per phase to permit testing of electromechanical
high impedance relays, and other high burden applications, with an
extended operating range up to 60 Amperes at 300 VA rms.
AC Voltage Output
Outputs are rated with the following Ranges:
Output Volts Power Max I
30 Volts 150 VA 5 Amps
150 Volts 150 VA Variable
2
300 Volts 150 VA 0.5 Amps
DC 150 Watts
Duty Cycle: Continuous
With two voltages in series
The output voltage and power doubles to provide 600 volts at
300 VA.
"PowerV" Voltage Amplifier Output Power Curves
“PowerV
TM
” Voltage Amplifier - Extended Power Range
The SMRT voltage amplifier provides a flat power curve from 30
to 150 Volts in the 150V range to permit testing of high current
applications such as panel testing.
Voltage Amplifier in Current Mode:
The voltage amplifier is convertible to a current source with the
following output capability. Output power ratings are specified in
rms values and peak power ratings.
Output Current Power Max V Duty Cycle
5 Amperes 150 VA 30.0 Vrms Continuous
(212 peak)
15 Amperes 120 VA 8.0 Vrms 90 Cycles
Phase Angle
Ranges: 0.00 to 359.99 degrees, Counter Clock Wise, or Clock
Wise rotation, or 0.00 to ±180.00 degrees
Accuracy: ±0.02° typical, ±0.25° max at 50/60 Hz
1
Megger reserves the right to change product specifications at any time.
2
PowerV
TM
voltage amplifier output current varies depending on the voltage setting on the 150 Volt range, see curve.
SPECIFICATIONS
1
Input Power
The input voltage rating varies depending upon the style number.
Universal units, the input voltage may be from 100 to 240 VAC,
± 10%, 50/60 Hertz. CE Marked units, the input voltage may be
from 220 to 240 VAC, ± 10%, 50/60 Hertz. Total maximum output
power will be limited for CE marked units . Input current required
varies with the number of output modules in use, load, and input
voltage value. With three VIGENS, the maximum input power is
1800VA.
Outputs
All outputs are independent from sudden changes in mains voltage
and frequency, and are regulated so changes in load impedance do
not affect the output. All amplifier outputs are isolated or floating.
The SMRT units can be ordered with the amplifier common returns
tied to chassis ground as an option.
Output Current Sources
The SMRT36 with three VIGEN modules can provide up to
six current sources; three high current/high power, and three
convertible channels providing lower current/high power. The per
channel output current and power ratings are specified in AC rms
values and peak power ratings.
Output Current Power Max V/Duty Cycle
1 Ampere 15 VA 15.0 Vrms Continuous
4 Amperes 200 VA (282 peak) 50.0 Vrms Continuous
15 Amperes 200 VA (282 peak) 13.4 Vrms Continuous
30 Amperes 200 VA (282 peak) 6.67 Vrms Continuous
60 Amperes 300 VA (424 peak) 5.00 Vrms 90 Cycles
DC 200 Watts
With three currents in parallel:
Output Current Power Max V/Duty Cycle
12 Amperes 600 VA (848 peak) 50.0 Vrms Continuous
45 Amperes 600 VA (848 peak) 13.4 Vrms Continuous
90 Amperes 600 VA (848 peak) 6.67 Vrms Continuous
180 Amperes 900 VA (1272 peak) 5.00 Vrms 90 Cycles
Current Amplifier Output Power Curve
With two currents in series:
The compliance voltage doubles to provide 4.0 Amperes at 100
Volts rms.