When you have finished making your configuration settings, click Save.
Shutdown Method There are three choices for the Shutdown method. Drop down
the list to select a choice. The meaning of each choice is
described, below:
Wake on LAN: This is a Safe Shutdown and Restart option. If
this is selected, when an Outlet is turned Off, the PN7212 /
PN7320 first sends a message to the computer telling it to
prepare for a shutdown; it then waits for the amount time set
in the Power Off Delay field to give the OS time to close down
before the computer is powered down to standby mode.
Likewise, when the Outlet is turned On, the PN7212 / PN7320
waits for the amount time set in the Power On Delay field,
then sends an Ethernet message to the computer connected
to the Outlet telling the computer to turn itself On.
Note: For Safe Shutdown and Restart, the computer must be
running Windows (98 or higher), or Linux, and the Safe
Shutdown program (available by download from our website),
must be installed and running on the computer.
System after AC Back: This is a Safe Shutdown and Restart
option. If this is selected, when an Outlet is turned Off, the
PN7212 / PN7320 first sends a message to the computer
telling it to prepare for a shutdown; it then waits for the
amount time set in the Power Off Delay field to give the OS
time to close down before the computer is powered down.
When the Outlet is turned On, the PN7212 / PN7320 waits for
the amount time set in the Power On Delay field, then sends
power to the server. When the server receives the power, it
turns itself on.
Note: For Safe Shutdown and Reboot, the computer must be
running Windows (98 or higher), or Linux, and the Safe
Shutdown program (available by download from our website),
must be installed and running on the computer.
Kill the Power: If this option is selected, the PN7212 / PN7320
waits for the amount time set in the Power Off Delay field, and
then turns the Outlet's power Off. Turning the power off
performs a cold (non-safe) shutdown.
MAC Address In order to use either of the Safe Shutdown and Restart
methods the MAC address of the computer connected to the
outlet must be filled in here.
Threshold Settings These fields are used to set the maximum, minimum, and
fluctuation current threshold settings. See Device Threshold
Settings, page 41 for a further explanation.
Server Diagnosis These fields are used to set up an ICMP ping command to
check if the outlet is functioning properly. See Server
Diagnosis, page 35 for a further explanation.