Instruction manual
IMP I IMP/P I SAM Hot Runner Controllers Instruction Manual
12
Installation
Never insert or remove the module from a mainframe with
the AC power on. Always switch the module or mainframe
to OFF. Hazardous potentials exist on components inside
both the module and mainframe. Always disconnect the
AC power to the mainframe when servicing.
SAM must be used in conjunction with a model “MFC”
communications-type mainframe, and one or more IMP
series microprocessor-based temperature controllers. It is
shipped from the factory ready to use. No special
preparation is required.
Installation Procedure:
1. Carefully unpack module. SAM may be plugged into
any unused zone of the mainframe.*
2. Release locking device by gently pulling push-pull
fastener away from the front panel.
3. Line up module printed circuit board with respective
mainframe guides. Insert module firmly, making sure
rear connectors are fully engaged.
4. Lock module into place by depressing push-pull
fastener.
*Note: SAM will work in any mainframe zone. A heater
connected to a zone with a SAM inserted will not affect
operation of the module.
SECTION 2 OPERATING INSTRUCTIONS
Model SAM Communications Module
2.1
CAUTION