Instruction manual
IMP I IMP/P I SAM Hot Runner Controllers Instruction Manual
4
The IMP controller also sends alarm status conditions to the SAM
auxiliary module for annunciation and remote control
functions.
Installation (IMP Series Only)
All IMP Series controllers are ready to use as shipped from
the factory. Prior to installation into a mainframe, make sure the
voltage, Hz, and degree options are as ordered and correspond to
the Product ID label.
Never insert or remove a controller from a mainframe
with the AC power on. Hazardous potentials exist on
components inside the mainframe and controller. Always
disconnect AC power to the mainframe when servicing.
To install a plug-in controller into a mainframe, release the
locking device on the lower edge of the unit by pulling the
plunger gently away from the panel. Align the upper and lower
edges of the printed circuit board on the controller with the
mainframe card guide slot and slide in until the rear connector
is completely engaged. Lock the controller into the frame by
depressing the plunger on the locking device.
Operation
Note: Any flashing display indicates that the controller has
detected a fault. Refer to section on Faults.
Automatic Closed-Loop Operation
1. Position Mode select switch to closed-loop (“O”).
2. Set temperature on Setpoint switch.
3. Turn on AC power.
4. After a short reset delay, the measured temperature will be
displayed. If the temperature is 30 ºF (17 °C) or more
below setpoint, the under temperature alarm display (lower
segment of the leftmost digit) will flash. If the temperature
1.2
CAUTION
1.3