Instruction manual
32
W i r i n g
IMPORTANT: All electrical wiring connections should be made
only by trained personnel using Class 1 wiring, and in strict
accordance with the National Electrical Code and local regula-
tions. Both of the incoming power lines should be fused with
2AG, 0.5 A maximum rated fuses.
The OTC25 controller has built-in circuitry to reduce the
effects of electrical noise (RFI) from various sources;
however, power and signal wires should always be kept
separate. We recommend separating wires into one bundle
for power (from line power and output) and one bundle for
signal (from thermocouple).
The OTC25 power supply accepts 100 through 250 Vac and
120 through 250 Vdc line power without any switch settings
or polarity considerations.
Figure 3. Wiring Connections
M o u n t i n g
Figure 2. Mounting Diagram
Before installing OTC25, ensure gasket seats evenly
around edges of unit and that there are no breaks or tears
in the gasket.
Insert the OTC25 through the front panel cutout, slide
mounting āUā bracket around unit and secure it with the
screws provided.
Gasket should be evenly compressed around all sides to
provide liquid-tight mounting.