Product Manual
Table Of Contents
34  2022 2096 26 
Instruction book 
3.3  Fuses and wire sizes 
Values shown here have been determined using National Electrical Code (NFPA 70). Local electrical 
code requirements my differ. Refer to your local electrical code. 
Volts Single Phase 
(V) 
Volts Three Phase 
(V) 
Fuses  
(Dual Element 
Time-Delay) 
(A) 
Wire Size 
(minimum) 
CR_5 
230 
- 
50 
10 
CR_5 
- 
200 
35 
14 
- 
230 
30 
14 
- 
460 
15 
14 
- 
575 
15 
14 
CR_7.5 
230 
- 
70 
8 
CR_7.5 
- 
200 
45 
10 
- 
230 
40 
12 
- 
460 
20 
14 
- 
575 
20 
14 
CR_10 
- 
200 
60 
10 
- 
230 
50 
10 
- 
460 
25 
14 
- 
575 
20 
14 
CR_15 
- 
200 
90 
6 
- 
230 
80 
8 
- 
460 
40 
12 
- 
575 
30 
14 
Motor Amperage 
This is the maximum Full-Load Three Phase Standard Motors, 1.15 SF. 
NEC Table 430.250 
Single Phase Full-Load Motor Amps are from NEC Table 430-248 
NEC Table 430.52 used for calculating Fuse size. 
NEC 240.6 Used to select Standard Fuse Sizes 
15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250, 300, 350, 400, 450, 
500, 600, 700, 800, 1000, 1200, 1600, 2000, 2500, 3000, 4000, 5000, and 6000 amperes. 
NEC 430.24 used to determine minimum wire size needed. 