Product Manual

2920 1339 02
12
Instruction book
AI. Air inlet
AO. Air outlet
4. Pictograph, manual condensate drain
5. Manual condensate drain valve
6. Pictograph, automatic condensate drain
7. Automatic condensate drain
Fig. 7. Rear view
M1. Refrigerant compressor
S3. Fan control switch
1. Hot gas by-pass valve
2. Condenser
3. Condensate trap
4. Heat exchangers
Fig. 8. Side view
2.3 Installation instructions
1. Install the dryer where the ambient air is as clean as possible
and where the temperature of the air will never exceed the
limits (see section 7). Keep the ventilation gratings of the
dryer free.
If necessary, take action to avoid external influences (wind,
draughts, etc.) through the ventilation gratings of the dryer,
as they may disturb the cooling air flow.
2. Connect the compressed air lines to the marked inlet and
outlet pipes of the dryer (Figs. 6 and 7). Provide an air
inlet valve and outlet valve. If a by-pass pipe and valve are
installed, the dryer can be serviced while by-passing the
dryer.
3. Fit manual condensate drain valve (5-Fig. 7).
Lay out the condensate drain hoses via a funnel towards a
drain collector to allow visual inspection. The hoses must
slope downwards. For draining of pure condensate, install
an oil/water separator; consult Atlas Copco.
If the condensate drain has been led down outside the
compressor room where it may be exposed to freezing
temperatures, it must be insulated.
4. A sticker dealing in short with the operating instructions
and explaining the pictographs is delivered with the
literature set. Affix the sticker next to the control panel.
Make yourself familiar with the instructions and pictographs
explained.
5. Fit the electric plug to the voltage supply cable. Plug in the
dryer.