Product Manual
Compressor type I
max
(1) Max fuse (1) I
max
(2) Max fuse (2)
K5/
HRC form II
K5/
HRC form II
V A A A A
GA 37 VSD+ 200 175.4 175 183.1 200
GA 37 VSD+ 230 175.4 175 183.1 200
GA 37 VSD+ 460 87.7 90 93.4 100
GA 37 VSD+ 575 70.2 70 73.2 80
I: current in the supply lines at maximum load and nominal voltage
(1): compressors without integrated dryer
(2): compressors with integrated dryer
Setting for circuit breakers
Q1 1 A
Q15 0.5 A
Fuse calculations for IEC are done according to 60364-4-43 electrical installations of buildings, part 4:
protection for safety- section 43: protection against overcurrent. Fuse sizes are calculated in order to protect
the cable against short circuit.
Fuse
calculations for cUL and UL: The indicated fuse size is the maximum fuse size in order to protect the
motor against short circuit. For cUL fuse HRC form II, for UL fuse class K5
Earthing
The earthing cable connected to the compressor (PE) should be minimum 10 mm
2
(according to EN 60204-1
section 828).
Cable sizing according IEC
The tables below indicate the current carrying capacities of cables for 3 commonly used installation methods,
calculated according to standard 60364-5-52 - electrical installations of buildings part 5 - selection and erection
equipment and section 52 - current carrying capacities in wiring systems.
The allowed currents are valid for PVC insulated cables with three loaded copper conductors (maximum
conductor temperature 70 °C).
Installation method B2 according table B.52.1.
Multi-core cable in conduit on a wooden wall
Maximum allowed current in function of the ambient temperature for installation method B2
Ambient temperature
Cable section 30 °C 40 °C 45 °C 50 °C 55 °C
4 mm² < 27 A < 23 A < 21 A < 19 A < 16 A
Instruction book
110 2920 7110 00