Product Manual

A possible ESi screen
3.19 Programmable settings
Compressor/motor
Minimum
setting
Factory
setting
Maximum
setting
Set-point 1 and 2, Workplace compressors bar(e) 4 7 13
Set-point 1 and 2, Workplace compressors psig 58 100 188
Set-point 1 and 2, Workplace Full-Feature
compressors
bar(e) 4 6.8 12.8
Set-point 1 and 2, Workplace Full-Feature
compressors
psig 58 99 186
Indirect stop level bar 0.1 0.3 1
Indirect stop level psi 1.45 4.35 14.5
Direct stop level bar 0.3 1 1.5
Direct stop level psi 4.35 14.5 21.8
Proportional band % 6 10 15
Integration time sec 5 6 10
Parameters
Minimum
setting
Factory
setting
Maximum
setting
Minimum stop time sec 5 5 30
Power recovery time sec 10 10 3600
Restart delay sec 0 0 1200
Communication time-out sec 10 30 60
Fan motor starts per day (air-cooled
compressors)
1 240 240
Instruction book
72 2920 7110 00