9 Technical data
9.1
Electric cable size
Attention
The voltage on the compressor terminals must not deviate more than 10% from the
nominal voltage.
It is however highly recommended to keep the voltage drop over the supply cables at
nominal current below 5% of the nominal voltage (IEC 60204-1).
If cables are grouped together with other power cables, it may be necessary to use
cables of a larger size than those calculated for the standard operating conditions.
Use the original cable entry. See section Dimension drawings.
The compressor is delivered with 3 m (10 ft.) cable and a fitting cable gland.
This cable gland is necessary to ensure the protection degree of the electric cubicle and
to protect its components from dust from the environment.
Local regulations remain applicable if they are stricter than the values proposed below.
G 7 G 11 G 15
Frequency
(Hz)
Voltage
(V)
Cable size Cable size Cable size
IEC
50 230
10 mm
2
16 mm
2
(16 mm
2
XLPE
or EPR)
16 mm
2
(16 mm
2
XLPE
or EPR)
50 400
4 mm
2
6 mm
2
6 mm
2
50 500
4 mm
2
6 mm
2
6 mm
2
60 460
4 mm
2
6 mm
2
6 mm
2
60 380
4 mm
2
6 mm
2
6 mm
2
CSA/UL
60 208-230 / 460 AWG8 AWG6 AWG4
60 575 AWG12 AWG10 AWG10
9.2 Settings for overload relay and fuses
G 7, G 11 and G 15
Frequency
(Hz)
Voltage (V) G7 G11 G15
IEC Star/Delta Over Load
relay FM1
(A)
Fuses FU
(aM)
Over Load
relay FM1
(A)
Fuses FU
(aM)
Over Load
relay FM1
(A)
Fuses FU
(aM)
50 230 18 40A 25,5 50A 30,5 63A
50 400 11 20A 15 32A 17,5 32A
50 500 6 20A 12 32A 14 32A