Product Manual
Table Of Contents
- Table of contents
- 1 Safety precautions
- 2 General description
- 3 Elektronikon Base Controller
- 3.1 ElektronikonTM Base Controller
- 3.2 Control panel
- 3.3 Icons used on the display
- 3.4 Main screen
- 3.5 Main function
- 3.6 Shutdown warning
- 3.7 Shutdown
- 3.8 Service warning
- 3.9 Scrolling through all screens
- 3.10 Calling up running hours
- 3.11 Calling up motor starts
- 3.12 Calling up module hours
- 3.13 Calling up loading hours
- 3.14 Calling up load solenoid valve
- 3.15 Calling up/resetting the service timer
- 3.16 Calling up/modifying pressure band selection
- 3.17 Calling up/modifying pressure band settings
- 3.18 Calling up/modifying the unit of temperature
- 3.19 Calling up/modifying the unit of pressure
- 3.20 Calling up/modifying backlight time
- 3.21 Activating automatic restart after voltage failure
- 3.22 Keyboard lock
- 4 Installation
- 5 Operating instructions
- 6 Maintenance
- 7 Adjustments and servicing procedures
- 8 Problem solving
- 9 Technical data
- 10 Instructions for use
- 11 Guidelines for inspection
- 12 Pressure equipment directives
- 13 Declaration of conformity
Minimum working pressure psig 58
Minimum ambient temperature ˚C 0
Minimum ambient temperature ˚F 32
9.4 Compressor data
G 7 (under reference conditions)
Compressor type G 7
Frequency Hz 50 60
Maximum (unloading)
pressure, Pack
bar(e) 7.5 10 13 7.4 9.1 10.8 12.5
Maximum (unloading)
pressure, Pack
psig 109 145 189 107 132 157 181
Maximum (unloading)
pressure, Full-Feature
bar(e) 7.25 9.75 12.75 7.15 8.85 10.55 12.25
Maximum (unloading)
pressure, Full-Feature
psig 105 141 185 103.7 128 153 178
Nominal working pressure bar(e) 7 9.5 12.5 6.9 8.6 10.3 12
Nominal working pressure psig 102 138 181 100 125 149 174
Set-point, thermostatic valve ˚C 75
Set-point, thermostatic valve ˚F 167
Temperature of air leaving outlet valve (approx.), Pack
Tank-mounted ˚C 33
Tank-mounted ˚F 91
Floor-mounted ˚C 60
Floor-mounted ˚F 140
Temperature of air leaving
outlet valve (approx.), Full-
Feature
˚C 24
Temperature of air leaving
outlet valve (approx.), Full-
Feature
˚F 75
Nominal motor power rating kW 7.5
Nominal motor power rating hp 10
Dryer power consumption at
full load, Full Feature units
kW 0.36 0.44
Dryer power consumption at
full load, Full Feature units
hp 0.48 0.59
Oil capacity l 3.2
Oil capacity US gal 0.84
Sound pressure level (ISO
2151 - 2004)
dB(A) 65 67
Instruction book
78 2920 7191 00